APPLICABLE CONTROLS
In case of installation to high ceiling
When the height of the ceiling to be installed exceeds
3.5m, adjustment of air volume is necessary. Set up
the high ceiling.
• Set according to the basic operation procedure
1
2
3
4
5
(
• Item code in Procedure specifies [5d].
• Select [Set data] in Procedure from "List of
installable ceiling height" in this Manual.
• For the item code in Procedure
• For the set data in Procedure
data of static pressure outside of the machine to be
set up from the table below.
(Exchange by wired remote controller)
Set data
0000
Standard (At shipment)
0001
High static pressure 1
To incorporate a filter sold separately
When mounting a filter sold separately, be sure to set
up the tap exchange according to the type of filter.
In this case, also follow to the basic operation
1
2
3
procedure (
• For the item code in Procedure
• For the set data in Procedure
data of filter to be incorporated from the table below.
Set data
0000
Standard filter (At shipment)
0001
Zeolite-3G deodorant filter
0003
High-efficiency filter (65%)
Deodorant filter
0006
Ammonium filter
6
).
3
, specify [5d].
4
, select the setup
3.5m or less
4.0m or less
4
5
6
).
3
, specify [5d].
4
, select the setup
Filter sold
separately
When using wireless remote controller
To exchange the static pressure, there is a method
other than the abovementioned method by wired
remote controller, which is to shift the short plug on the
indoor microcomputer P.C. board as shown in the
following table. Adopt this method in case of using a
wireless remote controller, etc.
* However, after exchanging once, be careful to shift
the short plug to the standard position (At shipment)
in order to return to the standard setup (follow to
E2PROM setup) though the setup for high static-
pressure 1, high static-pressure 2, or low static-
pressure can be arbitrarily performed.
It is necessary to rewrite data from the wired remote
controller sold separately in the set data "0000".
• Select by exchange of short plug on indoor
microcomputer P.C. board.
Short plug position
Set data
0000
0001
0003
0006
If selecting the set data 0006, do not discard the
removed short plug, but ask the users to keep it.
• Short plug position
(CN112, CN111, CN110 from the left)
36
Filter sold separately
Standard filter (At shipment)
Zeolite-3G deodorant filter
High-efficiency filter (65%)
Deodorant filter
Ammonium filter