DIMENSIONS

INSTALLATION

LOCATION
The CM707 thermostat is the control element of the heating
system and, therefore, MUST be located in a position with
good air circulation, at average room temperature and on an
inside wall, 1.5 metres above the floor level. Do not position
the CM707 thermostat near sources of heat (radiators, hot air
vents, TV or lights), near doors or windows, or in direct
sunlight.
MOUNTING
The CM707 thermostat can be mounted directly on the wall
surface or on to an electrical wall box.
WIRING
The CM707 thermostat is designed for fixed wiring only and
must be installed in accordance with the latest l.E.E.
regulations. Ensure the wiring connection to the supply is via
a fuse rated at no more than 5 amps and a Class "A" switch
(having contact separation of at least 3 mm in all poles).
IMPORTANT
1. The installer must be a trained service engineer.
2. Disconnect the power supply before beginning
installation.
6
CM707 CHRONOTHERM
EN0H 8558 UK07 R0 09/06