Starting DMS2

Starting DMS2

Current time setting

Set the current time of DMS2 system.
 "2009/01/01 01:01:01" is factory setting. Set the current time as DMS2 system time.
You can set DMS2 time in [System Settings]  [System environment setting]
(Refer to page 118~119)
If DMS2 time does not set as the current time, DMS2 may cause malfunction when
using Schedule or control logic management.
Connecting centralized controller & interface module
(1) Make sure that centralized controller communication cables(C1, C2) or interface module
communication cables(R1, R2) are connected.
 For communication between DMS2 and centralized controller/interface module,
centralized controller communication cable(C1, C2) or interface module
communication cable(R1, R2) should be connected.
(2) Execute tracking.
 DMS2 communicates with centralized controller and interface module and
brings information about installed indoor unit and outdoor unit.
 After tracking, you can use indoor unit control and other menu.
 For tracking, refer to [System Settings]  [Tracking] (Refer to page 134~144)
14