Thermsaver White Cased Oil Boiler Installation And User Manual page 13

White cased oil boiler
Table of Contents

Advertisement

FIT BOLTS
FIT CLIP
FIT SNORKEL TUBE
INTERNAL VIEW
5. With boiler in position pass the flue assembly
through the wall and bolt the bottom section of the
flue to the boiler, insuring that square gasket is in
between the boiler and the flue.
6. Attached the snorkel tube with clips to the flue.
7. Make sure that flue terminal protrudes through the
wall a minimum of 176mm for 80mm flue and
185mm for 100mm flue.
FLUE EXTENSION
The maximum horzontal flue level is 1450mm this
can be achieved using the following extension kits:
3 x kit 3 300mm extension
OR
1 x kit 6 950mm extension
8. Remove CF adaptor from burner and discard.
9. Fit the gasket and B F adaptor and connect snorkel
Tube.
N.B. Kit 8 45 degree bends must not be used on low
level balanced flue kits.
12
HORIZONTAL FLUE