H. Temperature Sensor
The temperature sensor is available as an optional accessory (ATS-5120) and is used to optimal charging over wide ambient
temperature range.
Fix the temperature sensor in a position on the battery which is not affected by other cooling or heating source.
Plug in the temperature sensor before switch on the charger to activate the temperature control function, never plug in the charger
during charging.
I. Cable Size Selection
Wire Size (AWG) Area (mm
10
5.26
8
8.37
6
13.3
4
21.2
2
33.6
1/0
53.5
2/0
67.4
4/0
Table: Selection of cable size and length versus current
2
)
Maximum one-way distance
(feet) for 2% Voltage loss
(24V 15A)
15.3
24
38
60
96
154
192
107
282
Maximum one-way distance
(feet) for 2% Voltage loss
(24V 20A)
11.5
18
29
45
72
116
144
212
Fig.5
Maximum one-way distance
(feet) for 2% Voltage loss
(24V 25A)
9.2
14.4
23
36
58
92
115
169