FOR 3 & 4-Wire Permanent Connections
2.
(3 & 4 - Wire Permanent Connections) Strip
insulation away from the ends of the permanent wiring
for Line 1, Line 2, Neutral (also strip ground wire on 4-
Wire Connections). Tighten all 3 wire leads to the
terminal block (Follow wire locations shown in Fig. 35).
iMPORTANT
NOTE; DO NOT LOOSEN the factory
installed nut connections
which secure the range
wiring to the terminal block. Electrical failure or loss of
electrical connection
may occur if these 3 nuts are
loosened or removed. NOTE: For 3=Wire Permanent
Connections skip Steps 3 & 4 and continue with
Step 5.
3.
(4=Wire Permanent Connection ONLY) Disconnect
the ground strap. Remove the factory installed ground
screw & plate to release the factory installed copper
ground strap from frame of the appliance. Cut and
discard the copper strap from the terminal block.
KEEP the ground screw, ground plate and go to Step
4.
4.
(4-Wire Permanent Connection ONLY) Connectthe
ground wire lead (Green) to the frame of the appliance
using the ground screw & plate as shown in Fig. 36.
Be sure to install using the same hole in the frame
where the ground screw was originally installed.
5.
(3 & 4 =Wire Permanent Connections}
Make sure all
connections are tightened securely and replace the
rear access cover (See Fig. 30).
A
GROUND
SCREW
.tp= GROUND
WIRE LEAD
PROPER
GROUND
FOR
4-WIRE
ND
PERMANENT
CONNECTION
Fig. 36
_=Tighten all 3
Terminal
wire leads
block
Line 2
plate
Ground
strap
NOTE: Non-terminated
field wire compression
connections must be set at approximately
22in./Ibs.
Always use 10 ga. wire or larger.
Pressure
Regulator
Location and
Installation
of
Gas
Supply
Pressure
Regulator
Flare
Adaptor
back o !
range
o
o
) Flexible Appliance
Conduit
(9
............. Adaptor
Shutoff
Black Pipe
Fig. 37
Off
9

Hide quick links: