Anti-Backflow Damper; Floor Installation; External Static Pressure Range - Coleman DGAA Installation Manual

High efficiency sealed combustion gas furnace (single stage downflow only) 56-90 mbh input (16.41 -26.38 kw)input
Table of Contents

Advertisement

129098-UIM-H-1011
NOTE: See label on coil panel for conversion and lighting instructions.
Obtain a temperature
rise within the ranges specified
on the name
plate.
AUTOMATIC
DAMPER
FURNACE
BASE
DUCT
CONNECTOR
NOTE:
FOR
BEST AIR
DELIVERY
INSTALL
DAMPER
WITH
BLADES
PARALLEL
TO SUPPLY
DUCT.
FIGURE 11: Anti-Backflow
Damper
INSTALLATION
RECOMMENDATIONS
1.
Remove the front panels and set the furnace onto the duct con-
nector. Slide it back until the rear of the unit engages the Iocator
bracket.
2.
Secure the front of the furnace with two screws at the mounting
holes provided.
3.
Secure the top of the furnace to a structural member using screw
through the strap at the back of the furnace. Strap may be moved
to any of the holes located along the top back of the furnace.
Installer
may provide
an equivalent
method,
such as screws
through the casing side.
The duct system is a very important part of the installation.
If the duct
system is improperly sized the furnace will not operate properly. The
ducts attached to the furnace plenum, should be of sufficient
size so
that the furnace operates at the specified
external static pressure and
within the air temperature rise specified on the nameplate.
Consideration
should be given to the heating capacity required and also
to the air quantity (CFM) required. These factors can be determined
by
calculating the heat loss and heat gain of the home or structure. If these
calculations
are not performed and the furnace is over-sized,
the follow-
ing may result:
1.
Short cycling of the furnace.
2.
Wide temperature fluctuations
from the thermostat setting.
3.
Reduced overall operating efficiency of the furnace.
The supply and return duct system
must be of adequate
size and
designed such that the furnace will operate within the designed air tem-
perature rise range and not exceed the maximum designed static pres-
sure. These values are listed in Table 2.
SECTION
II1: RETURN
AIR
REQUIREMENTS
CLOSET
INSTALLATIONS
Additional
Requirements
Additional
requirements
for floor and ceiling return system for closet
installed sealed combustion
heating appliance
are given in the next
paragraph.
kWARNING
HAZARD
OF ASPHYXIATION,
DO NOT COVER OR RESTRICT
FLOOR OPENING
TABLE 2: External Static Pressure Range
Input
Output
Nominal
Air Flow I
MBH
kW
MBH
kW
CFM cmm
In.W.C
kPa
56
16.4
45
12.9
1305 36.9
0.10
0.0249
70
20.5
56
16.4
1305 36.9
0.10
0.0249
77
22.5
62
18.0
1305 36.9
0.10
0.0249
90
26.3
72
21.1
1305 36.9
0.10
0.0249
Ext. Static Pressure
Minimum
Maximum
In.W.C
kPa
0.30
0.0747
0.30
0.0747
0.30
0.0747
0.30
0.0747
1. Std. Blower-High
Speed-No Coil.
IMPORTANT
The air temperature rise should be taken only after the furnace has
been operating
for at least 15 minutes.
Temperatures
should
be
taken 6" (15.2 cm) past the first bend from the furnace in the supply
duct. The return air temperature must be taken at the return air Iou-
vered door. Return static pressures can be taken by pushing probe
through the air filter on the Iouvered door.
BLEND
AIR INSTALLATIONS
If a blend air ventilation
system is installed, the 5" (12.7 cm) diameter
knockout in the top cover must be removed. The blend air damper is to
be placed on the top cover and secured with screws as shown in Figure
12. The power wires for the Blend Air Damper are inserted through the
7/8" (2.22 cm) hole in the top cover. The wires to the Blend Air Damper
will be connected as shown in Figure 20. Refer to the Blend Air Installa-
tion Manual to complete the installation.
BLEND AIR
FLEX DUCT
BLEND AIR
DAMPER
FLOOR
FIGURE 12: Floor Installation
8
Johnson Controls Unitary Products

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

DgahDgaa seriesDgah series

Table of Contents