CLEARANCES 
 
 
MAXIMUM PROTRUSION 
 
 
 
 
  *  For a 250 mm mantel shelf.  
  **  Where a fresh air intake is needed, we suggest you add a minimum of 102 mm (4'') to the 
width of the minimum masonry opening. 
  * **  If projection kit AC01323 (sold separately) is used L = 439 mm . If installed without projection 
kit L = 541 mm. 
Note  1:    From  door  opening.    The  depth  of  the  hearth  extension  in  front  of  the  wood  inbuilt  is 
included in the calculation of the floor protector's dimensions. 
Note 2: A min 80 mm air gap between the flue outer casing and the first timber stud above the 
fireplace insert is required. 
Note 3: The first internal wall stud must be 150 mm above the fireplace insert top and the front 
wall up to that first stud must be made of non‐combustible material. 
  _ _____________________________________________________________________________  3 5 
80 mm 
1250 mm 
1340 mm* 
40 mm 
40 mm 
FLOOR PROTECTION 
 
MINIMUM MASONRY 
 
 
500 mm 
975 mm  
OPENING 
622 mm 
781 mm** 
439 mm *** 
30 mm 
30 mm 
 