8 CLEARANCES TO HEAT‐SENSITIVE MATERIALS 
The clearances shown in this section have been determined by test according to procedures set 
out in safety standards AS/NZS 2918:2001 When the wood inbuilt is installed so that its surfaces 
are at or beyond the minimum clearances specified, combustible surfaces will not overheat under 
normal and even abnormal operating conditions.  
No part of the wood inbuilt may be located closer to combustibles than the minimum clearance 
figures given. 
8.1 LOCATION OF THE CERTIFICATION LABEL 
Since the information given on the certification label affixed to the appliance always overrides the 
information published, in any other media (owner's manual, catalogues, flyers, magazines and/or 
web  sites)  it  is  important  to  refer  to  it  in  order  to  have  a  safe  and  compliant  installation.  In 
addition, you will find information about your wood inbuilt (model, serial number, etc.). You can 
find  the  certification  label  on  the  side,  towards  the  front  of  the  outside  of  the  air  jacket  of  the 
inbuilt. 
To  access  the  certification  label,  the  faceplate  may  need  to  be  removed.  Therefore,  we 
recommend that you note the wood inbuilt's serial number on this manual, since it will be needed 
to  precisely  identify  the  version  of  the  appliance  in  the  event  you  require  replacement  parts  or 
technical assistance. 
8.2 POSITIONING THE UNIT 
It  is  necessary  to  have  a  floor  protection  made  of  non‐combustible  materials  that  meets  the 
measurements specified in table "FLOOR PROTECTION" (see Section 8.3. To determine the need 
to  add  floor  protection  (D)  beyond  the  hearth  extension,  you  must  do  the  following  calculation 
using the data in Table Data for floor protection calculation of this section: D = B ‐ (A ‐ C). If the 
value  (D)  is negative  or zero,  you  do  not  have  to  add  more  floor  protection  in  front  of  the  unit, 
because  the  masonry  fireplace  hearth  extension  is  large  enough.  If  the  value  (D)  is  positive,  you 
will need floor protection in front of the hearth extension at least equivalent to the result (D). 
Here  is  a  sample  calculation  to  determine  the  need  to  add  a  non‐combustible  materials  floor 
protection.  For  someone  whose  wood  inbuilt  would  protrude  76  mm  into  the  room  (C)  the 
calculation would be: 
 
Value D = B ‐ (A ‐ C) 
 
Value D = 500 mm ‐ (416 mm ‐ 76 mm) 
 
Value D = 500 mm ‐ 340 mm 
 
Value D = 160 mm 
Non‐combustible  floor  protection  of  at  least  160  mm  in  depth  must  be  installed  in  front  of  the 
fireplace hearth extension.  