PART B – INSTALLATION 
6 PRE‐INSTALLATION REQUIREMENTS 
6.1 MASONRY FIREPLACE 
The masonry fireplace must meet the minimum requirements found in the building code enforced 
locally,  or  the  equivalent  for  a  safe  installation.  Contact  your  local  Building  Inspector  for 
requirements in your area.  An inspection of the fireplace should include the following: 
1. CONDITION OF THE FIREPLACE AND FLUE SYSTEM: 
The masonry fireplace and flue system should be inspected prior to installation, to determine 
that  they  are  free  from  cracks,  loose  mortar,  creosote  deposits,  blockage,  or  other  signs  of 
deterioration.    If  evidence  of  deterioration  is  noted,  the  fireplace  or  flue  system  should  be 
upgraded and/or cleaned prior to installation. 
Masonry  or  steel,  including  the  damper  plate,  may  be  removed  from  the  smoke  shelf  and 
adjacent  damper  frame  if  necessary  to  accommodate  the  wood  inbuilt's  flue  liner,  provided 
that their removal will not weaken the structure of the fireplace and flue system, and will not 
reduce protection for combustible materials to less than that required by the building code. 
2. FLUE SYSTEM CAPS: 
Mesh type flue system caps must have provision for regular cleaning, or the mesh should be 
removed to eliminate the potential of plugging.  
3. ADJACENT COMBUSTIBLES: 
The  fireplace  should  be  inspected  to  make  sure  that  there  is  adequate  clearance  to 
combustibles,  both  exposed  combustibles  to  the  top,  side,  and  front  as  well  as  concealed 
combustibles,  in  the  flue  system  and  mantle  area.    Your  local  inspector  should  have 
information on whether older fireplaces are of adequate construction. 
4. OPENING SIZE: 
Refer to "MINIMUM MASONRY OPENING" (Section 8.5) for suitable size fireplace openings. 
6.2 ZERO‐CLEARANCE KIT 
5. INSTALLATION INTO AN EXISTING FACTORY‐BUILT ZERO‐CLEARANCE FIREPLACE: 
A 'built‐in' appliance is designed to be in contact with or built into a heat sensitive structure 
within a building. These types of appliances must be tested in a laboratory in accordance with 
AS/NZS 2918 to ensure their compliance with safety requirements. There is no such thing as a 
'standard'  (untested)  built‐in  appliance.  As  each  model  or  appliance  may  have  markedly 
different  installation  clearances  and  instructions,  it  is  extremely  important  to  follow  the 
manufacturer's  installation  instructions,  which  are  based  on  the  laboratory  tests  results.  The 
Matrix  inbuilt  can  only  be  installed  with  the  Osburn  Matrix  zero‐clearance  kit  (sold 
separately). See installation instructions provided with the kit. 
28  _ _____________________________________________________________________________   
 