Troubleshooting
LED ON OUTDOOR UNIT PCB
3MXS, 4MXS, 5MXS series
GREEN
MICROCOMPUTER
NORMAL
LED-A
LED1 LED2 LED3 LED4 LED5
GREEN NORMALLY FLASHING
RED
NORMALLY OFF
ON
FLASHING
OFF
IRRELEVANT
LED ON OUTDOOR UNIT PCB
2MXS series
GREEN
MICROCOMPUTER NORMAL
LED-A
GREEN NORMALLY FLASHING
ON
FLASHING
OFF
NOTE
1. Turn the power off and then on again. If the LED display recurs, the outdoor unit PCB is faulty.
2. Diagnosis marked
* Do not apply to some cases. For details, refer to the service guide.
39
RED
MALFUNCTION DETECTION
NOTE: The LED5 is only available in the 5M series.
DIAGNOSIS
NORMAL
CHECK INDOOR UNIT
[NOTE 1]
POWER SUPPLY FAULT OR [NOTE 2]
NORMAL
CHECK INDOOR UNIT
HIGH PRESSURE PROTECTOR WORKED OR FREEZE-UP IN
OPERATING UNIT OR STAND-BY UNIT
OVERLOAD RELAY WORKED OR HIGH DISCHARGE PIPE
TEMPERATURE
FAULTY COMPRESSOR START
INPUT OVERCURRENT
THERMISTOR OR CT ABNORMALITY
HIGH TEMPERATURE SWITCHBOX
HIGH TEMPERATURE AT INVERTER CIRCUIT HEATSINK
OUTPUT OVERCURRENT
REFRIGERANT SHORTAGE
LOW VOLTAGE TO MAIN CIRCUIT OR MOMENTARY VOLTAGE
LOSS
REVERSING SOLENOID VALVE SWITCHING FAILURE
FAN MOTOR FAULT
[NOTE 1]
POWER SUPPLY FAULT OR [NOTE 2]
DIAGNOSIS