Battery Replacement
When replacing the batteries on a SU1500RTXL2U, SU1500RTXL2UHV, SUINT1500RTXL2U,
SU2200RTXL2U,
SU3000RTXL2UHV or SUINT3000RTXL2U, qualified service personnel should refer to
"Battery Warnings" in the Safety section and follow this procedure:
1) Place the UPS horizontal with its control panel on the right side.
2) Remove the left snap-on cover panel (A).
3) Unscrew and remove the battery connector cover (B).
4) Disconnect battery connectors (C). Note: while batteries are disconnected, the UPS will
not provide battery backup in the event of a power outage.
5) Unscrew and remove the battery cover plate (D).
6) Unscrew and remove the battery retaining bracket (E).
7) Grasp pull-tab and pull out sliding battery tray (F).
8) Make a detailed sketch of the batteries and the polarity, color and connection of all cables.
Disconnect used batteries and dispose of them properly. Connect replacement batteries in
exactly the way the original batteries were connected. Note: Small sparks arcing between
battery connectors during battery replacement are normal. Reassemble the UPS by reversing
steps 1-7. Note: you may not receive full runtime until your new batteries have fully charged.
F
E
D
SU2200RTXL2U shown
10/3/2006
(continued)
SU2200RTXL2UHV,
SUINT2200RTXL2U,
C
13
3:32 PM
Page 13
SU3000RTXL2U,
B
A

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Smartonline suint1000rtxl2uSmartonline su1000rtxl2uhv

Table of Contents