Sp6 Single Phase Operation - ETC Sensor User Manual

Portable pack
Table of Contents

Advertisement

Phase A
connector
Phase B
connector
Phase C
connector
8
Setting up SP6 for single phase
operation
Phase connectors wired
for three phase operation
To convert a Sensor SP6 Portable Pack from three phase to
single phase operation, follow these steps:
1. Disconnect power from all Cam-Loks.
2. Remove all dimmer modules from the Portable Pack,
exposing the bus bars and connectors.
3. Remove the screws at the right ends of the two inch long
copper bars that connect the phase B connector to the
phase B bus bar. Loosen the screws at the left end of the
bars.
4. Rotate the top bar up and secure it to the phase A
connector.
5. Rotate the bottom bar down and secure it to the phase C
connector.
6. Tighten all screws to 40 inch/pounds of torque.
7. Replace dimmer modules.
8. Connect power to the A and C phase Cam-Loks. Do not
connect power to the B phase Cam-Lok.
Single phase operation is automatically detected by both
the CEM and the MPE, so no additional configuration is
necessary.