Component Tests; Thermostat Adjustments; Water Inlet Valve Test; Dual Probe Test/Dual Probe Liquid Level Controller Test - Cecilware ME10E-N Operation Manual

Automatic hot water boiler
Hide thumbs Also See for ME10E-N:
Table of Contents

Advertisement

A) Thermostat Adjustments:
The Thermostat is factory set for proper dispense temperature of 190° F
with the control shaft set to the maximum clockwise position. If field
adjustments are needed proceed as follows:
To DECREASE temperature, turn the control shaft slightly in the
COUNTERCLOCKWISE direction.
For qualified technicians ONLY:
Remove the knob and locate the Slotted Adjustment Screw inside the
hollow thermostat shaft. Using a narrow-bladed screwdriver, engage
slotted adjustment screw and turn it ¼ turn very slowly counterclockwise
(CCW). Allow a few minutes for the temperature to reach set level. The
Heater Light will go ON, indicating the heating element is activated, wait
for it to go OFF, indicating that the water has reached NEW set
temperature. Take a temperature reading and repeat if necessary.
B)

Water Inlet Valve Test

Turn power OFF. If the water level rises inside a partially filled tank, the
Water Inlet Valve is leaking. Disconnect wires from the Water Inlet
Valve coil and connect a 2 wire line cord to the terminals. Plug it into a
115V outlet. If water flows in and stops when you pull it out, the Valve
is working fine. Repeat this test a few times. The problem may be in
the Probe or Water Level Control Board. If the water does not flow in
when the cord is plugged into an electrical outlet, the Solenoid coil may
be damaged, opened or the valve may have an obstruction preventing
the water from flowing in. Clean or replace it.
C) Dual Probe Test
If lack of water persists, check the probe as follows:
Turn on the power and water supply. Check inside the tank to make
sure the water is below the Probe. Pull the BLUE wire and terminal
OFF the Probe rod. If water still does not flow after the wire is
disconnected from the Probe, the problem may be in the Solid State
Dual Level Control Board.
If water starts flowing into the tank, the Probe may be grounded, due to
excessive liming. Check with Ohm meter. Clean or replace probe.
D) Dual Probe Liquid Level Controller Test
Check the Controller as follows:
1.
Make sure there is power input to the Controller at the terminals AC1
& AC2
Your voltmeter should read 115 Volts. It should read the same at
terminals AC1 & FILL when the water level is low. This is the output
power to actuate the coil of the Solenoid Valve to open it. The lack of
voltage at terminals AC1 & L-LEVEL or H-LEVEL indicates that the
Controller is not working properly.
2. Make sure all wire connections are tight, including ground.
3. If after this, the Controller is still failing to open the Water Inlet Valve,
replace it.

COMPONENT TESTS

NUT
- CCW - DECREASES
TEMPERATURE
THERMOSTAT BULB
HOSE NUT ASSY
WATER INLET VALVE
DUAL PROBE
DUAL PROBE CONTROLLER
COUPLING
BLUE

Advertisement

Table of Contents
loading

This manual is also suitable for:

Me15e-nCme10e-nCme15e-n

Table of Contents