Tripp Lite SmartOnline 5kVA Owner's Manual page 25

Single-phase 5kva–6kva intelligent true on-line ups systems (rackmount/tower)
Hide thumbs Also See for SmartOnline 5kVA:
Table of Contents

Advertisement

Operation
(continued)
UPS Fault Shutdown Messages
CONDITION
+BUS >450V
Load <100%: +BUS < 320V; Load >100%: +BUS
<290V
-BUS >450V
Load <100%: -BUS <320V; Load >100%: -BUS <290V
BUS Voltage Over 500
Output Short
UPS Over Temperature
Ouput SCR Open Failure
Output Overload
Bypass SCR Short
Input SCR Rectifier Failure
Inverter Output Voltage Failure
Input Fuse Open
Output Fuse Open
Parallel ID Lost
On Battery Alarm
When in the On Battery Mode, the UPS power module will beep to inform you that it is using battery power to support connected
equipment. If its connected batteries are at more than half capacity, it will beep every two seconds. If its connected batteries are
below half capacity, it will beep twice a second. If its connected batteries are nearly depleted, the UPS power module will beep
continuously.
To silence the On Battery Alarm, press the "ON/MUTE" button.
Overload Messages
When the UPS detects an output overload, its LCD will switch to the following display:
The UPS will then begin a countdown. If the UPS is still overloaded at the end of the countdown, the UPS will automatically go to
Bypass Mode to protect its inverter. The duration of the countdown varies with the severity of the overload, as follows:
Bypass Messages
While in Bypass Mode, the UPS monitors its input voltage and passes that input power along to connected equipment. The UPS
will not provide battery backup in Bypass Mode.
If the output voltage deviates from an acceptable range (between 15% higher and 20% lower than nominal), the UPS displays the
condition on its LCD and stops supplying output power to its load. If power levels return to an acceptable level, the UPS resumes
supplying power to the load, and its LCD reports that output voltage was too high or too low at one time, but has returned to
nominal.
LCD DISPLAY MESSAGES
+ DC BUS HIGH SHUTDOWN
+ DC BUS LOW SHUTDOWN
- DC BUS HIGH SHUTDOWN
- DC BUS LOW SHUTDOWN
BUS OVP FAIL SHUTDOWN
OUTPUT SHORT SHUTDOWN
OVER TEMPERATURE SHUTDOWN
OUTPUT SCR FAIL SHUTDOWN
OVERLOAD SHUTDOWN
BYPASS SCR FAIL SHUTDOWN
RECTIFIER FAIL SHUTDOWN
INVERTER SHUTDOWN
I / P FUSE BROKEN SHUTDOWN
O / P FUSE BROKEN SHUTDOWN
PARALLEL FAULT SHUTDOWN
OVERLOAD!
LOAD = XXX% X.XXKW
Overload Condition
Countdown Duration
106% - 125%
1 minute
126% - 150%
30 seconds
>150%
Immediate
BYPASS VOLTAGE
CONDITIONS
>15% Higher
Than Nominal
>20% Lower
Than Nominal
25
LCD DISPLAY
MESSAGES
BYPS OUT OF VOLT
XXXV / XX.X HZ
BYPS OUT OF VOLT
XXXV / XX.X HZ