Chimney Requirements; Chimney Termination Requirements - Heat & Glo NORTHSTAR-BK Owner's Manual

Northstar epa certified woodburning fireplace
Hide thumbs Also See for NORTHSTAR-BK:
Table of Contents

Advertisement

A. Chimney Requirements
Vertical distances are measured from the base of the fire-
place as shown in Figure 8.2
Minimum overall straight height
Minimum height with single offset/
return
Double offset/return minimum height
Maximum height
Maximum chimney length between an
offset and return
Maximum distance between chimney
stabilizers
Maximum unsupported chimney
length between the offset and return
Maximum unsupported chimney
height above the fireplace
Maximum unsupported chimney
above roof
NOTICE: A maximum of two pairs of offsets and returns
may be used.
WARNING! Risk of Fire! You must maintain 2 in. (51
mm) air space clearance to insulation and other combus-
tible materials around the chimney system. Failure to do
so may cause overheating and fire.
6 ft (1.8 m) max.
unsupported
run
20 ft (6.10 m) max.
pipe between an
offset & return
Ceiling firestop
44 in.
(1118 mm)
to top of
standoffs
Figure 8.2

Chimney Requirements

4/20/11
13 ft
14.5 ft
20 ft
50 ft
20 ft
35 ft
6 ft
35 ft
6 ft
6 ft (1.83 m) max.
unsupported chimney
above roof
35 ft (10.7 m)
max. straight
unsupported
chimney height
14.5 ft (4.42 m) min. height/single offset-return
20 ft. (6.10 m) min. height/double offset-return
50 ft (15.24 m) max. height
Heat & Glo • NorthStar EPA Fireplace • 480-1081E
NOTICE: You must provide support for the pipe during
construction and check to be sure inadvertent loading has
not dislodged the chimney section from the fireplace or at
any chimney joint.
B. Chimney Termination Requirements
3.96 m
To determine the chimney components needed to complete your
particular installation, follow the steps below:
4.42 m
Determine the total vertical height of the fireplace installation. This
dimension is measured from the base of the fireplace assembly
6.1 m
to the point where the smoke exits the termination cap.
15.24 m
Subtract the effective height of the fireplace assembly from the
6.1 m
overall height of the fireplace installation (measured from the
base of the fireplace to the bottom of the termination cap, 13 ft.
(4m).
10.67 m
Refer to Table 8.1 to determine what components must be
selected to complete the fireplace installation.
1.83 m
Determine the number of ceiling firestops, stabilizers, roof
flashing, etc. required to complete the fireplace installation.
10.67 m
Table 8.1
1.83 m
HEIGHT OF CHIMNEY COMPONENTS
Chimney Stabilizer
SL3
Ceiling Firestops
FS338
FS339
FS340
Offsets/Returns
SL315
SL330
Roof Flashing
RF370
RF371
Chimney Sections*
SL306
SL312
SL318
SL324
SL336
SL348
* Dimensions reflect effective height.
CAUTION! Risk of Fire and/or Asphyxiation! DO NOT
connect this fireplace to a chimney flue servicing another
appliance. DO NOT connect to any air distribution duct or
system. These actions could cause overheating/fire in the
chimney flue, or release of exhaust fumes into the living
areas.
in.
mm
4-3/4
121
0
0
0
0
0
0
13-3/8
340
15-1/2
394
0
0
0
0
4-3/4
121
10-3/4
273
16-3/4
425
22-3/4
578
34-3/4
883
46-3/4
1187
Page 43