B. Clearances
WARNING! Risk of Fire! You must comply with all minimum air space clearances to combustibles as specified in Fig-
ure 6.2. DO NOT pack required air spaces with insulation or other materials.Framing or finishing material used on the
front of, or in front of, the appliance closer than the minimums listed.must be constucted entirely of non-combustible mate-
rials (i.e., steel studs, concrete boaed, etc.). Failure to comply may cause fire.
Figure 6.2
Page 36
Storm Collar
Roof Flashing
2 in. min.
(51 mm)
(attic)
2 in. (51 mm) min.
Ceiling Firestop
2 in. (51 mm) min.
0 in. to level
of standoffs
0 in.
to floor
Clearances to Combustible Materials
NOTICE: Chimney air kit is not shown, but is required.
Heat & Glo • NorthStar EPA Fireplace • 480-1081E
2 in. (51 mm) min.
Attic
Insulation
Shield
Ceiling Firestop
(ceiling)
2 in. (51 mm) min.
2 in. (51 mm) min.
Offset/Return with
hanger straps
(ceiling)
2 in. (51 mm) min.
Must have 2 in. (51 mm)
minimum clearance
1 in. (25mm) to side of appliance
(except at nailing flanges where it is 1/2 in. [13 mm])
to header
4/20/11