7.4.1

Battery replacement

Please refer to figure 7.4.1. Battery cabinet is the same for both power ratings, 6000VA and 10000VA.
NOTE
During battery replacement the UPS will not be able to support the load if a mains failure occurs! It
is recommended to switch off the load before disconnecting the DC connector as in section 4.3.2.
1.
Remove the battery cable
between battery cabinet(s)
and UPS.
2.
Remove
battery
between eventual further
battery cabinets.
3.
Replace the battery pack.
NOTE
To avoid battery malfunction, all battery packs have to be replaced! It's not possible to replace
only 1 pack. Avoid connections between new and old battery packs.
4.
Connect battery cables between additional battery cabinets.
5.
Connect battery cable between battery cabinet(s) and UPS.
6.
Check that battery data is set correctly via UPS monitoring software.
7.
The UPS is now ready to supply the load in case of mains failure.
General guidelines:
When replacing the batteries, use all of them of only the same type and size.
Never short the battery terminals. Shorting may cause the battery to burn.
When working with batteries remove watches, rings or other metal objects
and only use insulated tools.
Avoid charging in a sealed container.
Proper disposal of batteries is required: refer to your local codes for
disposal requirements.
Never dispose batteries in fire: they may explode.
Never disassemble or reassemble batteries; their contents (electrolyte)
may be extremely toxic. If exposed to electrolyte, wash immediately with
plenty of water, if eye contact occurs flush with water and contact a
physician.
The following table shows runtimes with up to 3 Battery Packs. 1 Battery Pack is the normal configuration.
Unit
GT 6kVA CE
GT 10kVA CE
modifications reserved
cables
Load
x1 (normal)
10%
201 min
25%
60 min
50%
26 min
75%
16 min
100%
10 min
10%
110 min
25%
37 min
50%
15 min
75%
8 min
100%
5 min
23
fig. 7.4.1
Don't throw batteries
away, treat them as
Number of battery packs
x2
346 min
150 min
61 min
38 min
26 min
255 min
87 min
37 min
22 min
15 min
User manual GT Series 6 - 10 kVA UPS 1.0 (GB)
harmful waste
x3
555 min
238 min
99 min
63 min
44 min
349 min
155 min
62 min
37 min
26 min