Sanyo KS0971 Technical & Service Manual page 32

Dc inverter split system air conditioner
Hide thumbs Also See for KS0971:
Table of Contents

Advertisement

7-1-2. Outdoor Unit
AVOID:
heat sources, exhaust fans, etc. (Fig. 4)
damp, humid or uneven locations.
DO:
choose a place as cool as possible.
choose a place that is well ventilated.
allow enough room around the unit for air intake/
exhaust and possible maintenance. (Fig. 5a)
provide a solid base (level concrete pad, concrete
block, 4"
1' 4" (10
minimum of 4" (10 cm) above ground level to
reduce humidity and protect the unit against
possible water damage and decreased service life.
(Fig. 5a)
Install cushion rubber under unit's feet to reduce
vibration and noise. (Fig. 5b)
use lug bolts or equal to bolt down unit, reducing
vibration and noise.
Install in a location where no antenna of a
television or radio exists within 10' (3 m).
7-1-3. Baffle Plate for the Outdoor Unit
(CLxx models only)
NOTE
It is recommended to use baffle plates for models
CL0971 and CL1271. The baffle plates are not
normally required for the other models.
When the outdoor unit is installed in a position
exposed to strong wind (like seasonal winds with low
air temperature in winter), baffle plates must be
installed at the rear of the outdoor unit. (Fig. 5c)
This unit is designed so that the fan of the outdoor
unit runs at low speed when the air conditioner is
operated at low outdoor air temperatures. When the
outdoor unit is exposed to strong wind, the system
pressure drops because of the freeze protector.
Baffle
plate
Air discharge
Fig. 5c
40 cm) beams or equal), a
6" min
Outdoor unit
Air intake
Min.
Air discharge
2" (5 cm)
Air intake
Concrete
or equal
Baffle
plate
32
NO
Exhaust fan
Hot air
Fig. 4
Min. 2" (5 cm)
Valve side
Min.
10" (25 cm)
Min.
8" (20 cm)
Fig. 5a
Cushion rubber
Fig. 5b
Heat source
Obstacle above
Min.
Min.
7' (2 m)
7' (2 m)
Ground
Min. 2" (5 cm)
Air intake
Anchor bolts
(4 pcs.)
Min. 4" (10 cm)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ks1271C0971Cl0971Cl1271C1271

Table of Contents