Download Print this page

Sanyo 09KLS71 Submittal Data

Split system indoor/outdoor wall mounted low ambient air conditioner
Hide thumbs

Advertisement

Split System Submittal Data
System: 09KLS71 Indoor/Outdoor: KS0971/CL0971
Wall Mounted Low Ambient Air Conditioner
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data (at 115V)
Power
V/PH/Hz
115/1/60
Circuit Ampacity
(A)
20
Fuse Size, Max.
(A)
20
Compressor
DC Rotary Inverter
No. used
1
R.L. Amps - L.R.
(A)
7.6 - 20
Crankcase Heater
(W)
20
Outdoor Unit
Fan type
Propeller
Dia. (in.) - No. Speeds
15-3/4-1
Type Drive - No. Speeds
DC Motor
No. Poles
(RPM)
8 - 750
No. Motors
(W)
50 - 1
(High)
883
CFM
F.L. Amps
(A)
0.6
Aluminum Fin & Copper Pipe
Coil Type
Corrugated Plate - Inner Riffeled
Fin Type - Pipe Type
2 - 18.1
Rows - F.P.I.
(sq.ft.)
3.1
Face Area
(in.)
5/16”
Tube Size
Indoor Unit
Fan type
Cross Flow
Dia. & Length (in.) - No. Speeds
3-11/16 24-31/32 - 1
No. Speeds
3 & Auto
No. Poles
(RPM, High)
4 - 1200
No. Motors
(W)
16 - 1
(HI/Med/Lo)
282/247/200
CFM
Indoor Sound Rating
(Hi) (dB-A)
34
(A)
0.45
F.L. Amps
Coil Type
Aluminum Plate Fin & Copper Tube
Fin Type - Pipe Type
Slit Plate - Inner Riffeled
Rows - F.P.I.
2 - 19.5
Face Area
(sq.ft.)
2.02
Tube Size
(in.)
9/32”
(in.)
23/32”
Drain Connection Size
Approval:
Date:
Construction:
Unit #:
Drawing #:
Refrigerant
R410A
Lbs. - R410a (outdoor unit)
2.09
Electric Expansion Valve
Control
Flare
Connection
50
Line Length, Max
23
Lift Difference, Max
Line Size
(in. O.D. Discharge)
1/4”
Line Size
(in. O.D. Suction)
3/8”
Dimensions
(in.)
H x W x D
Indoor Unit
(Uncrated)
11-7/32 x 32-15/32 x 7-7/16
(Crated)
13-25/32 x 35-7/16 x 10-1/32
Outdoor Unit
(Uncrated)
21-9/16 x 28-11/32 x 10-7/16
(Crated)
23-5/8 x 33-11/16 x 14-1/4
Weight
Indoor
Outdoor
Net
(lbs.)
19.8
72.8
(lbs.)
24.3
79.4
Shipping
Indoor
Outdoor
Shipping Volume
(cu.ft.)
2.82
6.36
Performance Data @ ARI Standard Conditions (115V)
Cooling
Total Capacity
(BTU/H)
9,000 (3,000-9,000)
Sensible Capacity
(BTU/H)
7,650
Latent Capacity
(BTU/H)
1,350
SEER
16
Dehumidification
(Pints/H)
3.4
Amps
(A)
7.6 (2.5-7.6)
Power Inputs
(W)
755 (250-755)
Outdoor Sound Rating
(dB-A)
46

Advertisement

loading

  Related Manuals for Sanyo 09KLS71

  Summary of Contents for Sanyo 09KLS71

  • Page 1 Split System Submittal Data System: 09KLS71 Indoor/Outdoor: KS0971/CL0971 Wall Mounted Low Ambient Air Conditioner Job Name: Location: Engineer: Submitted to: Submitted by: Reference: General Data (at 115V) Power V/PH/Hz Circuit Ampacity Fuse Size, Max. Compressor No. used R.L. Amps - L.R.
  • Page 2 Standard Available Available Available Indoor Air Intake Temp. Outdoor Air Intake Temp. 95F DB/71F WB 115F DB 67F DB/57F WB 0F DB Sanyo Commercial Solutions A Division of SANYO North America 1300 Michael Drive Wood Dale, IL 60191 USA www.sanyohvac.com...

This manual is also suitable for:

Ks0971Cl0971