MOTOR SHEAVE ADJUSTMENTS

V
, V
& 2
V
L
M
VP
ARIABLE
The driving and driven motor sheaves should be in align-
ment with each other and the shafts parallel.
V
& V
S
A
L
M
HEAVES
DJUSTMENT
1. Loosen set screw "B" using a 5/32" Allen key.
2. Making half or full turns from closed position, adjust
sheave pitch diameter for desired speed. DO NOT
OPEN MORE THAN SIX FULL TURNS.
3. Tighten set screw "B" securely over flat.
4. Carefully put on belts and adjust belt tension. DO NOT
FORCE BELTS OVER GROOVES.
5. Ensure all keys are in place and the set screws tight
before starting drive. Recheck set screws and belt
tension after 24 hours service.
NOTE: Future adjustments should be made by loosening the
belt tension and increasing or decreasing the pitch diameter
of the sheave by half or full turns as required. Readjust belt
tension before starting drive.
NOTE: Do not operate sheave with flange projecting beyond
the hub end.

MAINTENANCE

HIGH VOLTAGE!
D
ISCONNECT ALL POWER BEFORE SERVICING OR
. M
INSTALLING THIS UNIT
ULTIPLE POWER SOURCES MAY
. F
BE PRESENT
AILURE TO DO SO MAY CAUSE PROPERTY
,
DAMAGE
PERSONAL INJURY OR DEATH
T
O PREVENT PERSONAL INJURY OR DEATH DUE TO IMPROPER
,
INSTALLATION
ADJUSTMENT
,
MAINTENANCE
REFER TO THIS MANUAL
ASSISTANCE OR INFORMATION
SERVICE AGENCY OR THE GAS SUPPLIER
P
K
T
M
ITCH
EY
YPE
OTOR
C
B
VL & VM
WARNING
.
WARNING
,
,
ALTERATION
SERVICE OR
. F
OR ADDITIONAL
,
CONSULT A QUALIFIED INSTALLER
.
S
HEAVES
S
HEET METAL PARTS
HAVE SHARP EDGES
SERVICE PERSONNEL EXERCISE CAUTION
Your Self Contained Packaged Air Conditioner and Heat Pump
should operate for many years without excessive service calls
if the unit is installed properly. However it is recommended
that the homeowner inspect the unit before a seasonal start
up. The coils should be free of debris so adequate airflow is
achieved. The return and supply registers should be free of
any obstructions. The filters should be cleaned or replaced.
These few steps will help to keep the product up time to a
maximum. The Service section that follows should help in
identifying problems if the unit does not operate properly.
F
ILTERS
T
O PREVENT PROPERTY DAMAGE DUE TO FIRE AND LOSS OF
EQUIPMENT EFFICIENCY OR EQUIPMENT DAMAGE DUE TO DUST AND LINT
BUILD UP ON INTERNAL PARTS, NEVER OPERATE UNIT WITHOUT AN AIR
FILTER INSTALLED IN THE RETURN AIR SYSTEM.
Every application may require a different frequency of replace-
ment of dirty filters. Filters must be replaced at least every
three (3) months during operating seasons.
Dirty filters are the most common cause of inadequate heat-
ing or cooling performance. Filter inspection should be made
at least every two months; more often if necessary because
of local conditions and usage.
Dirty throwaway filters should be discarded and replaced with
a new, clean filter.
Disposable return air filters are supplied with this unit. See
the unit Specification Sheet or Technical Manual for the cor-
rect size and part number. To remove the filters, remove the
filter access panel on return side of the unit.
C
F
ABINET
INISH
Use a fine grade automotive wax on the cabinet finish to
maintain the finish's original high luster. This is especially
important in installations with extended periods of direct sun-
light.
,
14
CAUTION
,
,
SCREWS
CLIPS AND SIMILAR ITEMS INHERENTLY
,
AND IT IS NECESSARY THAT THE INSTALLER AND
.
CAUTION
M
AINTENANCE