Ac Wiring; Figure 15 Ac Terminals - Outback GS8048 Installation Manual

Radian series inverter/charger
Table of Contents

Advertisement

Installation

AC Wiring

The Radian inverter/charger's AC terminal block has nine positions for AC wires. The minimum
recommended wire size is #8 AWG (0.013 in
specific conditions. The largest size that can be used with the terminals is #6 AWG (0.021 in
16 mm
2
wire.
The inverter makes its AC connections using spring-loaded clamps. It is necessary to strip
approximately ½ inch (1 cm) of insulation from the end of each wire. Other tools are not required.
L1 and L2 Out
The terminals labeled L1 and L2 Grid are used to connect to the two utility grid "hot" wires. The L1
and L2 wires are usually black and red respectively, and read 120 Vac each when measured with
respect to neutral. In a standard service, L1 and L2 are 180 degrees out of phase, and should read 240
Vac when measured from one to the other.
The L1 and L2 Gen terminals are used to connect to the "hot" wires on a 120/240 Vac generator.
All system wiring must comply with national and local codes and regulations.
NOTE: The terminals are labeled for grid and generator due to common conventions, not because of
inverter requirements. Each input can accept any AC source as long as it meets the requirements of
the Radian inverter and the selected input mode. (See the Operator's Manual). If necessary, the Gen
terminals can accept grid power. The opposite is also true.
26
WARNING: Shock Hazard
Ensure there is only one AC neutral-ground bond at any time. Some codes
require the bond to be made at the main panel only. The GSLC is equipped with
its own bond, which may need to be removed.
IMPORTANT:
The AC input and output must be protected with branch-rated circuit breakers
of up to 50 Aac maximum size to meet NEC or other code requirements.
) or 10 mm
2
L1 and L2 Generator
Neutrals

Figure 15 AC Terminals

. Larger wire gauges may be required for
2
2
) or
L1 and L2
Grid
900-0021-01-00 Rev B

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents