Combustion Analysis - Ferroli OPTIMAX HE PLUS 18 S Instructions For Use, Installation And Maintenance

Wall-mounted gas fired, pre-mix condensing system boiler
Hide thumbs Also See for OPTIMAX HE PLUS 18 S:
Table of Contents

Advertisement

OPTIMAX HE PLUS 18 S
Opening the casing
To open the boiler casing, you need to follow the sequence given below
and the instructions of fig. 24.
1 Using a screwdriver, fully unscrew and remove the 2 screws "A "
2 Open by lowering the panel "B "
3 Lift and take off the casing "C "
Cleaning the boiler and burner
The body and burner must not be cleaned with chemical products or wire brushes. Special care must
be taken over all the sealing systems pertaining to the sealed chamber (gaskets, cable clamps, etc.). In
addition, it is necessary to pay attention after performing all these operations to check and carry out all
the phases of ignition and thermostat operation, the gas valve and circulation pump.
After these checks, make sure there are no gas leaks.

Combustion analysis

It is possible to analyse the combustion
through the air and flue sampling points
shown in fig. 25.
To make the measurement, it is neces-
sary to:
1) Open the flue sampling point
2) Insert the probe;
3) Press CH button
1) for 5 seconds to turn on TEST (Maxi-
mum Output) mode;
4) Wait 10 minutes for the boiler to sta-
bilize
5) Take the measurement.
6) Check boiler combustion also on minimum gas rate.
NAT GAS; CO2 Maximum reading should be 8.7 to 9.0% and at CO2 Minimum 8.5%
L.P.G; CO2 Maximum reading should be 9.5 to 10% and on Minimum 9.5%
Readings taken with an unstabilized boiler will cause measurement errors.
fig. 24
(part. 3, 4 - fig.
Cod. 3540L826 - 04/2009 (Rev. 00)
fig. 25
27