Alarm Configuration Parameters - York YLCA User Manual

Air-condensed water cooling units and heat pumps
Hide thumbs Also See for YLCA:
Table of Contents

Advertisement

1
User manual
1.2
Operating instructions µC2

1.2.11 Alarm configuration parameters

Parameters
P01
Alarm delay by flow switch at start-up.
P02
Alarm delay by flow switch with unit in operation.
P03
Alarm delay by low pressure switch at start-up.
Alarm reset
6= High and low pressure switch manual reset at
P05
third activation in one hour. Antifreeze control is
manually reset
Cool and heat cycle symbols:
1= "Sun" heat cycle, "Snowflake" cool cycle
P06
0= "Sun" cool cycle, "Snowflake" heat cycle
Digital input 1 for flow switch. Do not modify this
P08
parameter
Digital input 2 for the remote COOL/HEAT func‐
P09
tion. Do not modify this parameter
Low pressure alarm selection:
0= Inoperative with the compressor OFF
P15
1= Operative with the compressor OFF
P16
High-temperature alarm for return water
P17
High-temperature delay at start-up
High pressure alarm by transducer:
P18
0= Function disabled
P19
Low-temperature alarm for return water
Alarm activation for high and low water temper‐
ature at start-up:
P20
1= function enabled
0= function not enabled
20
Alarm configuration parameters
Description
Level
U
U
U
F
F
F
F
F
U
U
F
U
U
VS
Unit
Max.
63 (R/W)
Seconds
150
64 (R/W)
Seconds
120
65 (R/W)
Seconds
200
67 (R/W)
19 (R/W)
69 (R/W)
70 (R/W)
76 (R/W)
38 (R/W)
°C
77 (R/W)
Minutes
250
39 (R/W)
bar
99,9
40 (R/W)
°C
20 (R/W)
Min.
Value
0
20
0
5
0
60
6
1
0
1
1
9
1
0
1
80
-40
30
0
30
0,1
41
80
-40
10
1
0
0