Download Print this page

Emerson FANS Technical Information

Fans for condensing units

Advertisement

Quick Links

Date of last update: Jul-05
1
Introduction
Condensing units manufactured by Copeland are equipped with fan(s).
Various fan models are and were used.
That is to say that today, it is possible to meet various fan(s) on the after-sales market.
2
General information
Condensing units can be equipped with 1, 2 or 4 fans.
The complete fan consists of an external rotor motor with the fan blades permanently fixed to the rotor and the fan
guard. The grid has 4 feet to mount it on the condenser.
Fan motors are protected by a thermostatic switch. A single-pole bimetallic-element switch protects the motor
against damage from:
Motor overload
Over-voltage and under-voltage
Electrical and mechanical blockages
Inadequate cooling.
The fans protection is IP 54 and its insulation class is "F".
Most fans can be equipped with a speed controller connected to the condensing pressure.
3
Fans for Copeland Scroll and DWM Copeland semi-hermetic condensing units
The fan is positioned in order to blow the air from the condenser to the compressor, so the compressor additional
fan is not necessary any more.
NOTE: After connecting the condensing unit electrically, check the rotational direction. The fan must blow from
the condenser to the compressor.
NOTE: All fans presently used on condensing units are single-phase fans.
3.1
Single-phase fans
Single-phase fans are used since January 2003.
3.1.1
Technical data
As described in table 1, various fan models are used.
Blade
Power input
diameter
Fan model
mm
W
71
300
95
121
350
117
271
420
300
611
500
570
Table 1: Technical data – single-phase fans
Technical Information
F
C
F
C
A
N
S
F
O
R
O
N
A
N
S
F
O
R
O
N
Run capacitor
Voltage
µF / V
V (±10%) / Ph / Hz
EBM
220 - 240 / 1 / 50
3 / 400
220 - 240 / 1 / 50
4 / 400
220 - 240 / 1 / 50
5 / 400
220 - 240 / 1 / 50
10 / 400
U
U
D
E
N
S
I
N
G
N
I
T
S
D
E
N
S
I
N
G
N
I
T
S
Winding resistance Ω
Motor
current
(±10%), 25°C
Rotomatika
A
Main
2.5 / 400
0.44
115
0.54
72
6.3 / 400
1.35
25
2.4
8.5
Ref: CC7.5.1/0705/E
Application Engineering Europe
Auxilary
129
108
88
20.5
1/4

Advertisement

loading

Summary of Contents for Emerson FANS

  • Page 1 Inadequate cooling. The fans protection is IP 54 and its insulation class is "F". Most fans can be equipped with a speed controller connected to the condensing pressure. Fans for Copeland Scroll and DWM Copeland semi-hermetic condensing units The fan is positioned in order to blow the air from the condenser to the compressor, so the compressor additional fan is not necessary any more.
  • Page 2 Table 2: Technical data – three-phase fans “Old” units were delivered with three-phase fans as a standard, but it is possible to convert these fans into single- phase motor by the mean of a capacitor. The characteristics of this run capacitor are given in table 2.
  • Page 3 Figure 2: ∆ 230V ±15% / 3 ~ / 50-60 Hz Figure 3: Y 400V±15% / 3 ~ / 50-60 Hz - Y 500V±15% / 3 ~ / 50-60 Hz Three-phase fans can also be connected in single-phase thanks to a run capacitor. V2 Grey...
  • Page 4 CC7.5.1/0705/E Fans used on units manufactured before 1994 If you have an "old" unit manufactured before 1994, some fans are not supplied anymore, but you can replace them with the present fans. You can find the equivalent in the following cross reference (table 3).

This manual is also suitable for:

Copeland 71Copeland 121Copeland 271Copeland 611Copeland 65Copeland 145 ... Show all