Summary of Contents for Generac Power Systems 05176-0
Page 1
Not intended for use as Primary Power in place of utility or in life-support applications. DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!! Installation and Owner’s Manual Air-cooled Automatic Model: 05176-0 (13 kW NG, 15 kW LP) GENERAC POWER SYSTEMS, INC. DANGER ® Standby Generators ...
This manual contains pertinent owner’s information, including warranty, electrical diagrams, exploded views and lists of repair parts, for model: • 05176-0 – 13 kW NG, 15 kW LP , V-twin GT-990 Engine OPERATION AND MAINTENANCE It is the operator's responsibility to perform all safety...
Introduction ...Inside Front Cover Read This Manual Thoroughly ... IFC Contents ... IFC Operation and Maintenance ... IFC How to Obtain Service ... IFC Authorized Dealer Locator Number ... IFC Safety Rules ...2 Standards Index ... 3 Section 1 – General Information ...4 Unpacking/Inspection ...
IMPORTANT SAFETY INSTRUCTIONS Air-cooled 15 kW Generators SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted near the unit’s installation site. Safety should be stressed to all operators and potential operators of this equipment. ...
ELECTRICAL HAZARDS • All generators covered by this manual produce dangerous electrical voltages and can cause fatal electrical shock. Utility power delivers extremely high and dangerous voltages to the transfer switch as does the standby generator when it is in opera- tion.
Section 1 — General Information Air-cooled 15 kW Generators DANGER Only qualified electricians or contractors should attempt such installations, which must comply strictly with applicable codes, standards and regulations. UNPACKING/INSPECTION After unpacking, carefully inspect the contents for damage. • This standby generator set has been factory sup- plied with a weather protective enclosure that is intended for outdoor installation only.
4. Remove the engine air in baffle located on the left- hand side of the battery compartment. Two M6 screws are located on top of the baffle and two M6 screws are located on the inside of the baffle towards the back. 5.
Section 2 — Installation Air-cooled 15 kW Generators Remote monitoring functions are only available with the AUTO/OFF/MANUAL switch in the Auto or Manual position. Since the contacts are SPDT, it is possible to monitor either state of each alarm function. Relay 1: Engine running, normally closed.
Connect power source load conductors to clearly marked transfer mechanism terminal lugs as fol- lows 1. Connect UTILITY (NORMAL) power source cables to switch terminals N1, N2. 2. Connect customer LOAD leads to switch termi- nals T1, T2. Conductors must be properly supported, of approved insulative qualities, protected by approved conduit, and of the correct wire gauge size in accordance with applicable codes.
Section 3 — Post Installation Start-up and Adjustments Air-cooled 15 kW Generators Figure 2.4 – Battery Cable Connections NOTE: The generator is equipped with a battery trickle charger that is active when the unit is set up for automatic operation. With the battery installed and utility power source voltage available to the transfer switch, the battery receives a trickle charge while the engine is not running, to prevent...
3. Check utility power source voltage across termi- nals N1 and the transfer switch neutral lug; then across terminal N2 and neutral. Nominal line-to- neutral voltage should be 120 volts AC. 4. When certain that utility supply voltage is compat- ible with transfer switch and load circuit ratings, turn OFF the utility power supply to the transfer switch.
Section 3 — Post Installation Start-up and Adjustments Air-cooled 15 kW Generators CHECKING AUTOMATIC OPERATION To check the system for proper automatic operation, proceed as follows: 1. Set the generator’s main circuit breaker to it’s OFF (or open) position. 2. Check that the AUTO/OFF/MANUAL switch is set to OFF .
7. Turn utility power to the main distribution panel back on. This can be done by switching the ser- vice main breaker to the on or closed position. Allow the generator to shut down. Do not make any unnecessary adjustments. Factory settings are correct for most applica- tions.
Section 4 — Operation Air-cooled 15 kW Generators USING THE AUTO/OFF/MANUAL SWITCH (FIGURE 4.1) 4.1.1 “AUTO” POSITION Selecting this switch position activates fully automatic system operation. It also permits starting and exercising of the engine every seven days with the exercise timer (see "Generator Test Under Load").
• Retransfer to utility power source then occurs. F . Engine Cool-down Timer • When the load is transferred back to utility power source, the engine cool-down timer starts tim- ing. • The timer will run for about one minute, and the generator will then shut down.
Section 4 — Operation Air-cooled 15 kW Generators 4.4.2 CLOSE TO EMERGENCY SOURCE SIDE Before proceeding, verify the position of the switch by observing the position of the manual operation handle in Figure 4.2. If the handle is DOWN, the contacts are closed in the EMERGENCY (STANDBY) position.
7. Move the switch's main contacts back to their UTILITY position. For example, load connected to UTILITY power supply. Refer to "Manual Operation". Handle and operating lever of trans- fer switch should be in UP position. 8. Turn on the UTILITY power supply to transfer switch, using whatever means provided (such as a UTILITY main line circuit breaker).
Section 5 — Maintenance Air-cooled 15 kW Generators 4.8.3.1 Approximate Crank Cycle Times • 15 seconds ON • 7 seconds OFF • 7 seconds ON • 7 seconds OFF • Repeat for 45 seconds Approximately 90 seconds total 4.8.4 OVERSPEED This feature protects the generator from damage by shutting it down if it happens to run faster than the preset limit.
Figure 5.3 – Oil Drain Hose and Filter Drain Hose Oil Filter 3. After the oil has drained, replace the cap onto the end of the oil drain hose. Retain the hose in the clip. 4. Refill with the proper recommended oil (see "Changing the Engine Oil").
Section 5 — Maintenance Air-cooled 15 kW Generators BATTERY MAINTENANCE The battery should be inspected per the “Service Schedule”. The following procedure should be fol- lowed for inspection: 1. Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary. 2.
When valve clearance is correct, hold the pivot ball stud in place with the allen wrench and tighten the rocker arm jam nut. Tighten the jam nut to 174 in/lbs. torque. After tightening the jam nut, recheck valve clearance to make sure it did not change. Figure 5.6 - Valve Clearance Adjustment Pivot Ball Stud...
Section 5 — Maintenance Air-cooled 15 kW Generators 5.12.2 RETURN TO SERVICE To return the unit to service after storage, proceed as follows: 1. Set the generator’s main circuit breaker to its OFF (or OPEN) position. 2. Verify that utility power is turned off and that the AUTO/OFF/MANUAL switch is set to OFF .
Page 25
7 KW - 40 KW SMALL STANDBY GENERATOR SETS Following is a recommended maintenance schedule for small standby and residential generator sets from 7 kW to 40 kW in size, and applies to gas engine driven units. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application.
Page 26
Section 5 — Maintenance Air-cooled 15 kW Generators Maintenance Level 1 Tasks Recom- mended to be done monthly/ 10 hrs. 1. Disable the unit from operating per the first page warning. 2. Check the engine oil level. Adjust as necessary. 3.
Page 27
Maintenance Level 1 Tasks Recom- mended to be done monthly/ 10 hrs. 10. Test the engine and transfer switch safety devices. Correct and/or adjust as necessary. 11. Initiate an automatic start and transfer of the unit to site load and exercise it for at least 1 hour looking for leaks, loose...
Page 28
Section 5 — Maintenance Air-cooled 15 kW Generators Maintenance Level 1 Tasks Recom- mended to be done monthly/ 10 hrs. 16. Replace the engine air filter(s). 17. Perform a 5 minute no-load operational run of the unit looking for any post service problems.
TROUBLESHOOTING GUIDE Problem The engine will not crank. The engine cranks but will not start. The engine starts hard and runs rough. The AUTO/OFF/MANUAL switch is set to OFF , but the engine continues to run. There is no AC output from the generator.
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period.
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall continue for 24 consecutive months thereafter.
Page 52
• A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the genset. If a Non - Generac Power Systems, Inc. Transfer Switch is substituted for use and directly causes damage to the genset, no warranty coverage shall apply.
Need help?
Do you have a question about the 05176-0 and is the answer not in the manual?
Questions and answers