The definitions below describe the controls and functions of
the Generator Control Panel (Figure 4).
1.
Frequency Meter – Indicates the output frequency in
hertz (Hz). Normally 60 Hz.
2.
AC Ammeter – Indicates the amount of current the load
is drawing from the generator.
3.
AC Voltmeter – Indicates the output voltage present at
the Output Receptacles .
4.
Voltage Regulator Control – Allows ±15% manual
adjustment of the generator's output voltage.
5.
Engine Warning Display Module – This module
displays the following engine failures:
A. Overheat Lamp – This lamp goes ON
when the coolant is over 239
lamp goes ON during normal
operation of the generator, the
generator will immediately stop.
Check for possible trouble before
restarting engine.
B. Low Oil Pressure Lamp – During normal
operation of the generator this lamp
should remain OFF. After the oil
pressure rises after start-up, the
lamp will go OFF. This lamp goes
ON when the oil presure drops below
7.1 PSI.If this lamp is ever lit (ON) during normal
operation of the generator, the generator will
immediately shutdown. Check for possible trouble
before restarting engine.
C. Low Battery Fluid Lamp – This
lamp goes ON when the battery fails
to charge. If this lamp goes ON during
normal operation of the generator,
stop the engine and fill the battery
with distilled water to the
specified level.
D. Pre-Heat Lamp – This lamp
indicates when the engine is
ready for starting during cold
weather operating condition.
PAGE 20 — TLG-12SPX4— OPERATION AND PARTS MANUAL — REV. #1 (12/17/09)
TLG-12SPX4 — GENERATOR CONTROL PANEL
6.
7.
8.
9.
10. Ground Terminal - Ground terminal for Output
11. GFCI Receptacle – Provides 120 VAC output (20 amps
12. Auxillary Receptacle (for L5-30R) – Provides 120 VAC
o
F. If the
13. Auxillary Receptacle (for L6-30R) – Provides 240 VAC
14. Twist Lock Dual Voltage Receptacle (CS6369) –
18. Main Circuit Breaker – This three-pole, 50A main
Hour Meter – Indicates the number of hours machine
has been in use.
Fuel Guage – Indicates the amount of fuel in the
Generator.
Ignition Switch – Insert ignition key into this switch to
start engine.
Throttle Lever – This knob controls the speed of the
engine.
Receptacles.
max).
output (30 amps max).
output (30 amps max).
Provides 120/240 VAC output (50 amps max).
breaker is provided to protect the the Output
Receptacles from overload.