Load Application - MULTIQUIP GA-6REA Operation And Parts Manual

Robin gasoline engine
Table of Contents

Advertisement

Single Phase Load — 60 Hz
Always be sure to check the nameplate on the generators
and equipment to insure the wattage, amperage and
frequency requirements are satisfactorily supplied by the
generators for operating the equipment.
Generally, the wattage listed on the nameplate of the
equipment is its rated output. Equipment may require 130—
150% more wattage than the rating on the nameplate, as
the wattage is influenced by the efficiency, power factor and
starting system of the equipment.
If wattage is not given on the equipment's
name plate, approximate wattage may be
NOTE
determined by multiplying nameplate
voltage by the nameplate amperage.
WATTS = VOLTAGE x AMPERAGE
The power factor of this generators is 1.0 See Table 3 below
when connecting loads.
T
b a
e l
. 3
o P
y T
e p
f O
o L
d a
i S
g n
e l
p -
a h
e s
n i
u d
i t c
n o
m
o
o t
E
e l
t c
c i r
h
a e
e t
, s r
n i
a c
d n
s e
e c
a l
m
s p
F
u l
r o
s e
e c
t n
a l
m
p
, s
m
e
u c
y r
a l
m
s p
E
e l
r t c
n o
c i
d
i v e
e c
, s
o c
m
m
n u
c i
i t a
n o
e
u q
p i
m
e
t n
C
o
m
m
n o
o p
e w
t r
o o
s l
When using a combination of dual
receptacles, total load should not
NOTE
exceed the rated capacity of the
generator.
PAGE 16 — GA-6RE/GA-6REA A.C. GENERATORS — OPERATION & PARTS MANUAL — REV. #0 (06/06/05)
w
r e
a F
t c
r o
B
y
o L
d a
o P
w
r e
a F
t c
s r
. 0
- 4
. 0
5 7
t n
1
0 .
0
4 .
0 -
9 .
1
0 .
0
8 .
GA-6RE/GA-6REA — LOAD APPLICATION
To determine the running wattage for your load, multiply
the running wattage as indicated by steps 1, 2, and 3 below:
1.
INCANDESCENT LOADS
Lights, heaters and similar appliances.
Total the running wattage and multiply by 1.
Example:
29 light bulbs @ 100W each = 2.9 KW
use a 3 KW generator.
2.
SMALL MOTORS
Drills and other small power tools.
Total the running wattage and multiply by 2.
Example:
A 1 inch drill runs at 1 KW
use a 2 KW generator.
3.
LARGE MOTORS
Submersible pumps, table saws etc.
Total the running wattage and multiply by 3.
Example:
A conveyor belt runs at 8 KW
use a 24 KW generator.
CAUTION
CAUTION
CAUTION
CAUTION
CAUTION
r o
Motors and motor-driven equipment draw much greater
current for starting than during operation. Always use an
adequate size extension cable which can carry the
required load.
Extension Cables
When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used. Cables should be sized to allow for
distance in length and amperage so that the voltage
drop between the generators and point of use (load) is
held to a minimum . Use the cable selection chart (Tables
4 and 5 ) as a guide for selecting proper cable size.
NOTE
The idle control device is operated at a
minimum load capacity of 100W. If the
load capacity is less than 100W, place
the idle control switch in the OFF position.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ga-6re

Table of Contents