MULTIQUIP POWER WHISPERWATT DCA-25SSAI Parts And Operation Manual page 45

Whisperwatt generator
Table of Contents

Advertisement

Figure 45. Voltage Adjust Control Knob
12. The ammeter (Figure 46) will indicate zero amps with no
load applied. When a load is applied, this meter will
indicate the amount of current that the load is drawing
from the generator's alternator.
0
Figure 46. Ammeter (No Load)
13. The engine oil pressure gauge (Figure 47) will indicate
the oil pressure (kg/ cm
operating conditions the oil pressure is approximately
25 psi.
Figure 47. Oil Pressure Gauge
14. The coolant temperature gauge (Figure 48) will indicate
the coolant temperature. Under normal operating
conditions the coolant temperature is between 165 and
215 degrees Fahrenheit.
Figure 48. Coolant Temperature Gauge
PAGE 45 — DCA-25SSAI — PARTS AND OPERATION MANUAL— FINAL COPY (06/29/01)
DCA-25SSAI — GENERATOR START-UP PROCEDURE
40
20
60
75
A
2
) of the engine. Under normal
WATER
TEMP
15. The tachometer (Figure 49) will indicate the speed of
the engine when the generator is operating. Under normal
operating conditions this speed is approximately 1800
RPM's.
Figure 49. Engine Tachometer
16. Turn the MAIN, GFCI and LOAD circuit breakers to
their ON position (Figure 50).
Figure 50. Main and GFCI Circuit Breakers
17. Observe the generator's ammeter (Figure 51) and verify
it reads the anticipated amount of current with respect
to the load. The ammeter will only display a current
reading if the load is in use.
0
Figure 51. Ammeter (Load)
18. The generator will run until manually stopped or an
abnormal condition occurs.
40
20
60
75
A

Advertisement

Table of Contents
loading

Table of Contents