Westerbeke 8.0KW-60Hz Service Manual page 87

Single and three phase d-net diesel generators
Hide thumbs Also See for 8.0KW-60Hz:
Table of Contents

Advertisement

BT GENERATOR VOLTAGE REGULATOR ADJUSTMENTS
Description
The voltage regulator is an advanced design which ensures
optimum AC generator performance.
It
is equipped with
complete protection circuitry to guard against operating
conditions that could be detrimental to the AC
~enerator;
......... 1I0LIllGE REGULATOR
Volts
TIris potentiometer is used to adjust output voltage. At proper
engine operating speed the output voltage should be held at
±1
%
from a no-load condition to a full rated generator output
and from power factor 1.0 - 0.8 with engine drive speed
variations up to -6%. Prior to starting the engine, turn the
VOLT and STAB tiimmers (using a mini phillips screw-
driver) fully in a counter clockwise (Minimum) direction
until you feel them hit their stops.
Tum
the AMP and
HER1Z trimmers completely clockwise (Maximum) in the
same manner. With the generator running at no-load, at-
normal speed, and with VOLT adjust at minimum, it is
possible that output voltage will oscillate. Slowly rotate the
VOLT adjust clockwise. The voltage output will increase and
stabilize. Increase the voltage to the desired value. In this
situation, only the green LED will stay lit.
Stability
TIris potentiometer permits variation of the regulator's
response to generator load changes so as to limit overcom-
pensation and obtain a miuimum recovery time to the normal
voltage output
In order to adjust the regulator stability the generator must be
running at no-load and the output must be monitored.
Turn the STAB adjust slowly clockwise until the voltage
starts to fluctuate. At this point rotate the STAB adjust coun-
terclockwise until the voltage is stable within 1 or 2 tenths of
a volt.
red
~
green
-
yellow '-
Hertz
Am~
Stab
Vol!
VOLTAGE REGULATOR DIAGRAM
Amp-Hertz
These two adjustments are used in conjunction with the two
protection circuits in the voltage regulator that are indicated
by the illumination of colored LED lights.
1. Delayed overload protection (yellow LED).
2. Low speed protection (red LED).
Both systems have an intervention threshold which can be
adjusted using the respective potentiometer. Each of the two
circuits are able to cause an adequate reduction in excitor
voltage to safeguard the excitor windings and prevent their
overheating.
.
The overloall protection system has a delay which permits
temporary overloading of the generator during times such as
motor start-up or other similar load surge demands. The regu-
lator also has a third LED (green), that glows during genera-
tor operation to indicate correct operation of the regulator
with the generator.
Setting the Overload Protection
In order to set the AMP overload protection, the generator
must be loaded to its full output rating.
'1. Load.tha generator to its rating, then decrease the speed of
the engine
by
10.10% (54 Hertz on 60 hertz units, 45
hertz on 50 hertz units).
.
2. Rotate the AMP adjustment counterclockwise until it hits
its stop. Wait about 15-20 seconds after which the AC out-
put of the generator should drop and the yellow LED light
should come on.
3. Slowly rotate the AMP adjustment clockwise until the
output voltage increases to approximately 97% of the volt-
age output at the start of the adjustment. At this point the
yellow LED light should come on.
4. Return to nominal speed, the yellow LED will tum off
and the generator voltage will rise to its normal value.
Should this not happen, repeat the adjustment.
NOTE: When changing from 60 hem. to 50 hem. operation,
remove the 60 hertz jumper bar from the regulator board.
Setting the Underspeed Protection
NOTE: lftheunit is operating at 60 Hem. ensure that the
jumper strap is in place on the regulator board between the
two 60 Hem. terminals. In order to adjust the 'underspeed
setting, the generator should be running at no-load.
1.
To adjust the underspeed Qow frequency) protection circuit,
lower the engine speed at 90% of its nOimai running speed
(54 hertz on 60 hertz nnits, 45 hertz on 50 hertz units.
2. Rotate the Hertz adjustment counterclockwise slowly until
the generator's AC output voltage starts to decrease and at
the same time the red "LED" light comes on.
3. Increase the engine speed to its norma! speed (frequency).
The red "LED" light will go out and the AC voltage out-
put will return to normal.
With the above adjustments made, the regulator should func-
tion ilomtally.
~
WESTERBEKE
Engln/'$
&
Generator$
81
.

Advertisement

Table of Contents
loading

Table of Contents