If Hose Slopes Downhill - Honeywell TrueSTEAM Professional Installation Manual

Hide thumbs Also See for TrueSTEAM:
Table of Contents

Advertisement

Available languages

Available languages

Installation Guide
appendIx a: remote InstallatIon
Cut a slit in the insulation half way
around the hose.
Do not cut into the
rubber steam hose.
3 in. minimum clearance from nozzle
outlet to duct.
Nozzle at upward pitch.
Minimum upward
pitch of 2 in. per ft.
12 in.
Avoid sharp kinks and
prevent bends.
Clearance hole for hose and insulation.
Seal off unconditioned space with
grommet (not provided) or caulk.
6 in. of straight
vertical rise.
Clamp
69-2285EFS—03
24 in. open air downstream.
1-3/4 in. hole
Clamp
On straight runs, use perforated angle
iron. Otherwise, secure hose every 12 in.
using provided hooks.
Always install nozzle so the
outlet is pointed up.
Do not route the steam
hose through the hole in the
mounting plate.
On straight runs, use
perforated angle iron.
Otherwise, support
hose every 12 in. using
provided hooks.
Always consult and follow local
plumbing codes for drain pipe
size and maximum temperature
requirement.
Insert the hose clamp into
the slit and hook it onto the
rubber hose.
M28674

If hose slopes downhill...

Downward slope can not be more than
3 ft below humidifier steam outlet.
Provide a 212°F rated Tee at the
lowest point. Do not use plastic Tee.
Minimum 6 in.
Minimum 2 in.
24
Hose clamps at
every connection.
Minimum upward
pitch of 2 in. per ft.
Nozzle at
upward pitch.
Clamps
Water in elbow.
M28675

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents