Honeywell S7999D SOLA User Manual page 46

Sola operator interface display
Hide thumbs Also See for S7999D SOLA:
Table of Contents

Advertisement

Table 60. Configurable Parameters. (Continued)
Parameter
Comment
Heat
Enabled
exchanger
Disabled
high limit
enable
Heat
-40 °F to 266 °F
exchanger
(-40 °C to 130 °C)
high limit
setpoint
Heat
Recycle & delay
exchanger
Recycle & delay with retry limit
high limit
Lockout
response
Heat
0 to 100
exchanger
retry limit
Heat
___hour ___min ___sec
exchanger
high limit
delay
CH anticon-
Enabled
densation
Disabled
enable
CH anticon-
Normal (no change)
densation
CH pump forced off
pump
CH anticon-
-40 °F to 266 °F
densation
(-40 °C to 130 °C)
setpoint
DHW anti-
Enabled
condensa-
Disabled
tion enable
DHW anti-
Normal (no change)
condensa-
DHW pump forced off
tion pump
DHW anti-
-40 °F to 266 °F
condensa-
(-40 °C to 130 °C)
tion setpoint
Anticondensa
Anticondensation is more
tion Priority
important than (check those
that apply):
Stack limit
Delta T limit
Slow start
Forced rate
Outlet high limit
65-0315—02
Table 60. Configurable Parameters. (Continued)
Table
Page
#
#
Parameter
22
21
CH frost
protection
enable
DHW frost
protection
enable
Lead Lag
frost
protection
enable
Outdoor frost
protection
setpoint
Lead Lag
frost
protection
rate
CH pump
frost overrun
23
22
time
DHW pump
frost overrun
time
Annunciation
enable
Annunciator
(1–8) location
Annunciator
(1–8) short
name
Annunciator
(1–8) name
46
Comment
Enabled
Disabled
Enabled
Disabled
Enabled
Disabled
-40 °F to 266 °F
(-40 °C to 130 °C)
(applicable for CH only)
___%
___hour ___min ___sec
___hour ___min ___sec
Enabled
Disabled
01 - Annunciator 1
02 - Annunciator 2
03 - Annunciator 3
04 - Annunciator 4
05 - Annunciator 5
06 - Annunciator 6
07 - Annunciator 7
08 - Annunciator 8
PII - Pre-Ignition ILK
LCI - Load Control Input
ILK - Interlock
Up to 3 characters
Up to 20 characters
Table
Page
#
#
24
22
25
23

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents