Delta T Limit Configuration
Parameters
(R7910 Hydronic Control Only)
Table 20 displays other limit parameters. Use the left and right
arrows to switch between Inlet to Outlet Flow and Exchanger
to Outlet Flow. The parameters are the same for all pumps.
Fig. 40. Delta T Limit configuration.
Table 20. Delta T Limit
Configuration Parameters.
Parameter
Delta T enable
Enabled
Disabled
Delta T degrees
0 °F to 234 °F (-17 °C to 112 °C)
Delta T delay
___hour ___min ___sec
Delta T response
Recycle & delay
Recycle & Delay with retry limit
Lockout
Comment
21
Table 20. Delta T Limit
Configuration Parameters. (Continued)
Delta T retry limit
0–100
Delta T rate limit
Enabled
enable
Disabled
Delta T inverse limit
___hour ___min ___sec
time
Delta T inverse limit
Recycle & delay
response
Recycle & delay with retry limit
Lockout
T-Rise Limit Configuration
Parameters
Table 21 displays T-Rise limit parameters.
Table 21. T-Rise Limit Configuration Parameters.
Parameter
Outlet T-rise enable
Enabled
Disabled
Heat exchanger T-
Enabled
rise enable
Disabled
T-rise degrees
0 °F to 234 °F (-17 °C to 112 °C)/sec
T-rise response
Recycle & delay
Recycle & delay with retry limit
Lockout
T-rise retry limit
0 to 100
T-rise delay
___hour ___min ___sec
Heat Exchanger High Limit
Configuration Parameters
Table 22 displays T-Rise limit parameters.
Table 22. Heat Exchanger High Limit
Configuration Parameters.
Parameter
Heat exchanger high
Enabled
limit enable
Disabled
Heat exchanger high
32 °F to 250 °F (0 °C to 121 °C)
limit setpoint
Comment
Comment
65-0315—02