DCA-125SSJU SERIES — GENERATOR START-UP PROCEDURE (MANUAL)
15. The coolant temperature gauge (Figure 59) will indicate
the coolant temperature. Under normal operating
conditions the coolant temperature should be between
165 and 215 degrees Fahrenheit ( Green Zone ).
Figure 59. Coolant Temperature Gauge
16. The tachometer gauge (Figure 60) will indicate the
speed of the engine when the generator is operating.
Under normal operating conditions this speed is
approximately 1800 RPM's.
Figure 60. Engine Tachometer Gauge
17. Place the main , GFCI , and aux . circuit breakers in the
"ON" position (Figure 61).
Figure 61. Main, Aux. and GFCI
Circuit Breakers (ON)
DCA-125SSJU SERIES (STANDARD)— PARTS AND OPERATION MANUAL— REV. #4 (06/03/03) — PAGE 43
18. Observe the generator's ammeter (Figure 62) and verify
it reads the anticipated amount of current with respect
to the load. The ammeter will only display a current
reading if a load is in use.
Figure 62. Ammeter (Load)
19. The generator will run until manually stopped or an
abnormal condition occurs.