Temperature Resistance Chart Table - Pentair UltraTemp User Manual

Hide thumbs Also See for UltraTemp:
Table of Contents

Advertisement

42
Problem or Symptoms
Higher than Normal Head Pressure, lower than
normal suction pressure with high superheat
and very cold or frosty distributor tubes, may
have no Alarm.
Lower than Normal Head Pressure, higher
than normal suction pressure with cold suction
line and compressor and no superheat, may
have no Alarm.
Unusually higher than normal current.
Low current with high superheat.
Unit runs, but trips continously.
Problems and Corrective Action (3 Phase Units Only)
Problem or Symptoms
Unable to turn Heat Pump ON. Display is
Blank. Unit will NOT start.
Compressor making a loud or unusual noise or
sounds during operation. Fan is turning, no
cool air discharge out of top of heater. Unit
ON, and Set Temperature is above Actual, but
Unit is not heating.
°F
OHMS
°F
0
85,387
51
10
62,479
52
20
46,225
53
30
34,561
54
40
26,100
55
41
25,391
56
42
24,704
57
43
24,037
58
44
23,391
59
45
22,764
60
46
22,156
61
47
21,566
62
48
20,993
63
49
20,438
64
50
19,900
65
NOTE: Any service must be done by an authorized service agency person.
Installation and User's Guide
Possible Cause
TXV stuck closed.
TXV stuck open.
TXV stuck closed/partially closed, insufficient water
flow, system overcharged.
Unit undercharged.
Wires not connected properly.
Possible Cause
Incorrect Wiring.
Faulty Phase Monitor.
Loose wire on Phase Monitor, either from the supply
input power or the output side.
Compressor running Backwards. This usually
happens if the compressor wire harness is
disconnected for possible repaire or replacement.
* Temperature Resistance Chart
OHMS
°F
OHMS
19,377
66
13,136
18,870
67
12,809
18,377
68
12,491
17,899
69
12,182
17,435
70
11,882
16,985
71
11,589
16,548
72
11,305
16,123
73
11,029
15,711
74
10,761
15,310
75
10,500
14,921
76
10,246
14,543
77
9,999
14,176
78
9,758
13,820
79
9,525
13,473
80
9,297
Corrective Action
1. Disconnect TXV bulb from suction line (SL), have it in your hand, if
pressures go back to normal, then reinstall the bulb on suction line (it
may have some debris stuck in the port). For adjustable TXVs open
adjustable valve, it may remove the debris and set it back to original
position.
2. If (1) does not work, recover the charge, remove bulb from SL,
unscrew TXV head, shake it, if rattles, replace head
(PN KT-45-ZGA), if not, replace TXV and filter dryer and charge
appropriately.
1. Check to see if TXV bulb is firmly attached to suction line, if loose,
attach firmly by tightening the clamp over the bulb and suction line.
2. If (1) above does not work, reclaim charge and replace TXV and
filter dryer with nameplate charge.
See Possible Cause column for: TXV stuck closed, Insufficient
water flow, and Unit overcharged.
Find source of refrigerant leak and fix. Pull vacuum and charge.
Fix the miswire as per the Wiring Diagrams.
Corrective Action
Check the Light on Phase Monitor inside the electrical box. If red,
switch two of the Input wires. Any two of the three can be switched.
Call dealer or factory for advice before attempting to replace parts.
Replace Phase Monitor.
Check the Light on Phase Monitor inside the electrical box. If the Light
is Red, fix the supply power loose end. If the Light is Green, fix the
output loose wire.
Switch any two of the three wires on the compressor side of the
Contactor.
°F
OHMS
°F
81
9,076
96
82
8,861
97
83
8,651
98
84
8,447
99
85
8,249
100
86
8,056
101
87
7,867
102
88
7,684
103
89
7,506
104
90
7,333
105
91
7,164
106
92
6,999
107
93
6,839
108
94
6,683
110
95
6,530
120
OHMS
6,382
6,238
6,097
5,960
5,827
5,697
5,570
5,446
5,326
5,208
5,094
4,982
4,873
4,664
3,758

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents