SPECIFICATIONS
Table 7 Electrical Output
Output Connections
Nominal Outputs
Voltage Regulation (Normal mode)
Voltage Regulation (Battery mode)
Efficiency (Normal mode)
Efficiency (Battery mode)
Frequency
Frequency Regulation (Normal mode)
Frequency Regulation (Battery mode)
Output Overload (Normal mode)
Output Overload (Bypass mode)
Output Overload (Battery mode)
Voltage Waveform
Harmonic Distortion
Transfer Time
Power Factor
Load Crest Factor
36
HP R3000v UPS User Guide
50 or 60 Hz, auto-sensing or configurable as a frequency converter
Sync with line ±3 Hz of nominal line frequency
(outside this range: ±0.1 Hz of auto-selected nominal frequency)
100–102%: Activates Overload alarm. (Level 1)
102–129%: Load transfers to Bypass mode after 12 seconds. (Level 2)
130–149%: Load transfers to Bypass mode after 2 seconds. (Level 3)
>150%: Load transfers to Bypass mode after 100 ms. (Level 4)
NOTE: Default configuration transfers immediately to bypass at >102%.
100–109%: Activates Overload alarm. (Level 1)
110–129%: UPS shuts down after 5 minutes. (Level 2)
130–149%: UPS shuts down after 15 seconds. (Level 3)
>150%: UPS shuts down after 300 ms. (Level 4)
100–102%: Activates Overload alarm. (Level 1)
102–129%: UPS shuts down after 12 seconds. (Level 2)
130–149%: UPS shuts down after 2 seconds. (Level 3)
>150%: UPS shuts down after 100 ms. (Level 4)
<3% THD on linear load; <5% THD on non-linear load
S
164201731 Rev 1
(8) IEC 320-10A, (1) IEC 320-16A
200/208/220/230/240V
(voltage configurable or auto-sensing)
3 kVA, 2.1 kW
±2%
Nominal output voltage ±3%
>88%
>84%
±0.1 Hz of auto-selected nominal frequency
Sine wave
Online mode: 0 ms (no break)
0.7
3 to 1