NOTE: A small amount of arcing may occur when connecting the internal batteries. This is
normal and will not harm personnel. Connect the cables quickly and firmly.
2. Connect the internal battery connector (see Figure 9).
Connect red to red, and black to black. Press the two parts tightly together to ensure a
proper connection.
Figure 9 Connecting the UPS Internal Batteries
3. If you are installing ERMs, see the section, "Connecting the ERM(s)," before continuing
with the UPS installation.
4. Replace the UPS right front bezel.
To replace the bezel, verify that the ribbon cable is protected and (if ERMs are
installed) the ERM cable is routed through the knockout on the bottom of the bezel.
Slide the bezel to the left until it aligns with the left front bezel. Tighten the two captive
screws on the right side of the right front bezel.
5. If you are installing power management software, connect your computer to one of the
communication ports using the appropriate cable (supplied). See page 21 for more
information.
6. If your rack has conductors for grounding or bonding of ungrounded metal parts,
connect the ground cable (not supplied) to the ground bonding screw. See Figure 13
on page 15 for the location of the ground bonding screw.
7. Continue to "UPS Initial Startup" on page 14.
HP R3000v UPS User Guide
S
164201731 Rev 1
INSTALLATION
11