Preliminary Thank you for purchasing Gateway product. Gateway is a versatile Protocol converter / Data sharer with Windows based configuration Software. This manual will help you to safely install, configure and operate Gateway Products. All the safety warnings and precautions must be followed to ensure proper unit performance and personal safety.
Page 3
Rev. changed from 4 to 5: Sartorius to GWY-00 cable added. Rev. changed from 5 to 6: Baumuller Drive to GWY-00 cable added. Rev. changed from 6 to 7: Baumuller Drive (2 WIRE) to GWY-00 cable added. Rev. changed from 7 to 8: Thomson Technology Controller to GWY-00 cable added.
8.10 GE VERSAMAX PLC TO GWY-00 (EC-P-002A-00) ............ 44 8.11 IDEC MICRO3 TO GWY-00 (EC-P-025A-00) ............... 45 8.12 KEYENCE KV PLC TO GWY-00 (EC-P-018-00) ............46 8.13 LG MASTER K SERIES PLC TO GWY-00 (EC-P-037-00) ......... 47 8.14 MITSUBISHI FX SERIES PLC TO GWY-00 (EC-P-008B-00) ........48...
Page 5
8.21 RHEONIC MASS FLOW METER TO GWY-00 (EC-P-091B-00) ......55 8.22 SIEMENS S7-300 SERIES PLC TO GWY-00 (EC-P-077-00) ........56 8.23 SIEMENS STEP 7 MICRO (S7-200) PLC TO GWY-00 (EC-P-029-00) ....57 8.24 TELEMECHANIQUE TSX-07/TSX-37 PLC TO GWY-00 (EC-P-026A-00) .... 58 8.25 TOSHIBA T1 LINK PORT TO GWY-00 (EC-P-046A-00) ..........
The intention of this Operation Manual is to provide a guide for Safe installation, Configuration and operation of Gateway. This manual is applicable for General purpose Gateway (Part# GWY-00) units. If your Gateway Part# is other than GYW-00, please refer to ‘Addendum for Special Gateways’ section for hardware specific details.
The typical configurations include the followings: 1. PLC to PLC Communication X Protocol Y Protocol PLC1 PLC2 Protocol Converter Example: GWY-00 by Renu Electronics 2. PLC as a Master in Modbus Network X Protocol Node 1 Motor Drive Protocol Converter...
Gateway Specifications Power Supply : 24 VDC +/- 10 %, 100 mA max Communication : Two ports as follows: PLC1 : RS232C / RS422 / RS485 / CMOS For configuration and PLC communication PLC2: RS232C / RS422 / RS485 / CMOS For PLC communication Indications : PLC1 LED - for PLC1 port status...
PENDING PLC2 Slot for DIN rail clamp clamp GWY-00 24VDC +/- 10% EARTH Renu Electronics Pvt. Ltd. Survey No. 2/6, Baner Road, Pune-411045 INDIA (RS232/RS485/CMOS) PLC 2 GWY-00 DIN rail DIN rail plate clip Following drawing shows the dimensional details of Gateway with DIN rail plate 50.5mm...
Page 12
PENDING PLC2 GWY-00 GWY-00 24VDC 24VDC +/- 10% +/- 10% EARTH EARTH Renu Electronics Pvt. Ltd. Renu Electronics Pvt. Ltd. Survey No. 2/6, Baner Road, Survey No. 2/6, Baner Road, Pune-411045 INDIA Pune-411045 INDIA (RS232/RS485/CMOS) (RS232/RS485/CMOS) PLC 2 PLC 2 Follow instructions given below: Attach the DIN rail plate to the unit using the clamps on the DIN rail plate.
Gateway is a 24VDC powered unit. Power should be applied on the PCB Terminal block on the Gateway unit. Power rating is +24VDC +/- 10%, 100mA max. For specification of non-GWY-00 models, please refer to ‘Addendum for Special Gateways’. Please follow the instructions given below when making power supply...
Communication Ports Gateway unit has two communication ports. Both the ports have DB9 type connectors and are compatible with RS232C, RS422, RS485 and CMOS signal levels. PLC1 (also known as COM1) and PLC2 (also known as COM2) have exactly the same pin outs which are as shown below: PLC1 / PLC2 ports RX- (RS422/RS485) RX+ (RS422/RS485)
IBM download cable for downloading configuration in Gateway. If any change in the current / working project is made, user must download the changed project in Gateway. Pin details of IBM download cable for GWY-00 are as follows: DB9 Male (Gateway) DB9 Female (IBM)
Page 17
Download PLC1 driver, PLC2 driver and project within 10 seconds after power-on. METHOD II Short pins 3 and 4 on PLC1 port of GWY-00 for at least 1 second after power-on. Remove the short. Now GWY-00 permanently waits for IBM download. Connect IBM download cable.
UNDERSTANDING GATEWAY FEATURES In this chapter..Gateway Modes Multi-dropping of devices using Gateway Repeat Cycle Control Word Error Indication Bit Communication parameters Status LEDs...
Gateway Modes Gateway has two modes of operation: Master-Master and Master-Slave. Before explaining these modes further Master and Slave concept should be explained. Master: Master is a Device which initiates communication. Slave: Slave is Device which processes Master’s query, takes necessary action and responds to the query, if necessary.
Example 4.1 Toshiba T series – Modbus Master: This configuration can be used to make Toshiba PLC function as a Modbus Master. Configure Gateway ports as: PLC1 Protocol: Toshiba T Series PLC and PLC2 Protocol: Modbus (Master). PLC1 of Gateway is configured as Toshiba T series master protocol so T series PLCs can be connected to PLC1 of Gateway.
Page 21
Example 4.2 Toshiba T series - Modbus Slave This configuration can be used to make Toshiba T series PLC function as a Modbus Slave. Configure Gate- way ports as: PLC1 Protocol - Toshiba T Series Master PLC2 Protocol - Modbus Slave. So the device connected on PLC1 will be a Toshiba T series PLC acting as a slave and device connected on PLC2 will be Modbus Master.
Multi-dropping of Devices using Gateway Gateway supports multidropping on both the ports. Following illustration explains multidropping of devices on Gateway ports. Devices with protocols that support networking can be multi-dropped on RS485 port of Gateway. Maximum 31 devices can be networked on Gateway RS485 ports. Node 1 Node 1 Motor...
Repeat Cycle User can control Block execution by using the Repeat Cycle field. This number decides whether the Block will be executed in each cycle. Larger the number lower the priority of the Block. Range for Repeat Cycle setting is 1-99. Repeat Cycle = 1 …………...
Error Indication Bit This feature enables detection of communication breaks during error free communication between Gateway and two devices. Communication breaks can occur due to no cable connection, wire faults, device power failure at both ends of Gateway. An Error bit can be designated in each external device connected to Gateway.
Project Setup This Chapter explains, how a simple Gateway project can be created and tested. To develop a Gateway system, select appropriate Gateway model depending on the system requirements. A new project can be created as follows: 1. Define the Gateway System: Protocol of Device(s) connected to PLC1 Protocol of Device(s) connected to PLC2 2.
Page 27
The Block edit screen should appear. Now create a block for data transfer. Please see screen below. Download this project and communication drivers into Gateway. Observe that when the inputs of PLC1 are turned ON the corresponding outputs of PLC2 are turned ON.
Example 2: Higher Level Controller (Modbus master) to PLC (Modbus slave) This project allows a higher level controller (acting as a Modbus master) to read devices and registers from a PLC and to write to devices and registers in a PLC. Select a Toshiba T1 PLC on the PLC1 port and a Modbus Slave on the PLC2 port.
Example 3: PLC (Modbus master) to Other Device (Modbus slave). This project allows the PLC to read the current temperature from the PID controller and write a set point into the PID controller. Assume Modbus Holding register 400001 contains the actual temperature. Assume Modbus Holding register 400002 is for the set point.
System Requirements: System Requirement for Gateway setup software are: Windows Version: Microsoft Windows XP / 2000, Windows 7 / VISTA (32/64 bits) Processor: PENTIUM or higher Hard disk Space: 5 MB or more Serial Mouse: Required RAM: 64 MB or more Display resolution: 800 X 600 (VGA) or better Display colors:...
Wiring Diagrams User must ensure correct wiring for problem-free operation of Gateway. Each device being connected to Gateway has a unique communication port. Pin outs of communication ports of gateway are given in section 2.3. Port details of the other devices can be found in the device manual. Gateway has RS232, RS422, RS485 and CMOS compatible communication ports, so user can directly connect any device with these communication signals.
AB SLC DH485 PORT TO GWY-00 (EC-P-007-00) GWY-00 SIDE AB SLC SIDE 2 mtr. DB9 MALE 8 PIN MODULAR CONNECTOR Shield Wire SIGNALS Pin # Pin # SIGNALS SHIELD 8 PIN MODULAR CONNECTOR Shield Wire R.H.S. VIEW DB9 MALE FRONT VIEW...
AB MICROLOGIX SERIES PLCs TO GWY-00 (EC-P-027A-00) GWY-00 SIDE AB MICROLOGIX SIDE 2 mtr. MINIDIN 8 PIN MALE DB9 MALE (RS232) Shield Wire (RS232) SIGNALS Pin # Pin # SIGNALS DB9 MALE Shield Wire 8 PIN MINIDIN CONNECTOR PINOUTS PINOUTS...
A B SLC DF1 PORT TO GWY-00 (EC-P-027B-00) AB SLC SIDE GWY-00 SIDE 2 mtr. DB9 MALE DB9 FEMALE Shield Wire (RS232) (RS232) SIGNALS Pin # Pin # SIGNALS DB9 MALE DB9 FEMALE Shield Wire to DB9 body PINOUTS PINOUTS...
AROMAT FP1 TO GWY-00 (EC-P-015B-00) ARPMAT FP1 GWY-00 SIDE SIDE 2 mtr. DB9 MALE DIN CONNECTOR MALE Shield Wire (RS485) (RS485) SIGNALS Pin # Pin # SIGNALS Shield Wire DIN CONNECTOR PINOUTS DB9 MALE PINOUTS...
AROMAT FP2 TO GWY-00 (EC-P-015D-00) AROMAT FP2 SIDE GWY-00 SIDE 2 mtr. DB9 MALE DB9 MALE (RS232) Shield Wire (RS232) SIGNALS Pin # SIGNALS Pin # Shield Wire to DB9 body DB9 MALE PINOUTS...
GE 90 SERIES PLC TO GWY-00 (EC-P-002-00) GWY-00 SIDE GE 90 SERIES SIDE 2 mtr. DB9 MALE Shield Wire (RS232) DB15 MALE (RS485) SIGNALS # Pin # Pin # SIGNALS EARTH DB9 MALE Shield Wire PINOUTS DB15 MALE PINOUTS...
GE VERSAMAX PLC TO GWY-00 (EC-P-002B-00) GWY-00 SIDE GE VERSAMAX SIDE 2 mtr. DB9 MALE DB9 MALE Shield Wire (RS232) (RS232) SIGNALS Pin # SIGNALS Pin # Shield Wire DB9 MALE PINOUTS...
8.10 GE VERSAMAX PLC TO GWY-00 (EC-P-002A-00) GE VERSAMAX GWY-00 SIDE SIDE 2 mtr. 8 PIN MODULAR CONNECTOR DB9 MALE (RS232) (RS232) SIGNALS Pin # Pin # SIGNALS 8 PIN MODULAR CONNECTOR PINOUTS DB9 MALE R.H.S. VIEW FRONT VIEW PINOUTS...
8.13 LG MASTER K SERIES PLC TO GWY-00 (EC-P-037-00) GWY-00 SIDE LG MASTER PLC SIDE 2 mtr. DB9 MALE DB9 MALE Shield Wire (RS232) (RS232) SIGNALS Pin # SIGNALS Pin # Shield Wire DB9 MALE PINOUTS...
8.14 MITSUBISHI FX SERIES PLC TO GWY-00 (EC-P-008B-00) GWY-00 SIDE MITSUBISHI FX PLC SIDE 2 mtr. DB9 MALE Shield Wire DB25 MALE (RS485) (RS485) SIGNALS Pin # Pin # SIGNALS DB9 MALE Shield Wire PINOUTS DB25 MALE PINOUTS...
8.17 MOISTURE ANALYSER TO GWY-00 (EC-P-098-00) GWY-00 SIDE MOISTURE ANALYSER SIDE 2 mtr. WIRE OUTS DB9 MALE SIGNALS FROM PLC Shield Wire (RS232) Pin # SIGNALS Pin # SIGNALS YELLOW GREEN BLACK DB9 MALE PINOUTS...
8.20 RHEONIC MASS FLOW METER TO GWY-00 (EC-P-091A-00) GWY-00 SIDE RHEONIC MASS FLOW METER SIDE 2 mtr. DB9 MALE DB25 MALE Shield Wire (RS232) (RS232) SIGNALS Pin # Pin # SIGNALS DB9 MALE Shield Wire PINOUTS DB25 MALE PINOUTS...
8.21 RHEONIC MASS FLOW METER TO GWY-00 (EC-P-091B-00) RHEONIC MASS FLOW GWY-00 SIDE METER SIDE 2 mtr. DB9 MALE DB9 MALE Shield Wire (RS422) (RS232) SIGNALS Pin # Pin # SIGNALS Shield Wire DB9 MALE PINOUTS...
8.22 SIEMENS S7-300 SERIES PLC TO GWY-00 (EC-P-077-00) SIEMENS S7-300 SIDE GWY-00 SIDE 2 mtr. DB9 MALE DB9 MALE Shield Wire (RS485) (RS485) SIGNALS Pin # Pin # SIGNALS DB9 MALE Shield Wire to DB9 body PINOUTS Note: These details are also applicable to Siemens S7-200...
8.23 SIEMENS STEP 7 MICRO (S7-200) PLC TO GWY-00 (EC-P-029-00) SIEMENS S7-200 SIDE GWY-00 SIDE 2 mtr. DB9 MALE DB9 MALE Shield Wire (RS485) (RS485) SIGNALS Pin # Pin # SIGNALS DB9 MALE Shield Wire to DB9 body PINOUTS Note: These details are also applicable to Siemens S7-300...
8.25 TOSHIBA T1 LINK PORT TO GWY-00 (EC-P-046A-00) GWY-00 SIDE TOSHIBA T1 LINK PORT SIDE 2 mtr. WIRE OUTS DB9 MALE SIGNAL FROM PLC Shield Wire (RS485) Pin # SIGNALS Pin # SIGNALS YELLOW GREEN BLACK WHITE BLUE DB9 MALE...
8.27 TOSHIBA T2 LINK PORT TO GWY-00 (EC-P-046B-00) TOSHIBA T2 LINK PORT SIDE GWY-00 SIDE 2 mtr. DB9 MALE Shield Wire (RS232) DB15 MALE (RS485) Pin # SIGNALS # Pin # SIGNALS DB9 MALE Shield Wire PINOUTS DB15 MALE PINOUTS...
8.28 TOSHIBA T2 PLC TO GWY-00 (EC-P-019B-00) TOSHIBA T2 GWY-00 SIDE SIDE 2 mtr. DB9 MALE DB9 MALE (RS485) Shield Wire (RS232) SIGNALS Pin # Pin # SIGNALS DB9 MALE Shield Wire PINOUTS Note: These details are also applicable to Siemens S7-300...
8.30 METTLER TOLEDO TO GWY-00 (EC-P-103-00) GWY-00 SIDE METTLER TOLEDO (COM1) SIDE 2 mtr. WIRE OUTS DB9 MALE SIGNAL FROM Shield Wire (RS232) METTLER TOLEDO Pin # SIGNALS Pin # SIGNALS YELLOW GREEN BLACK DB9 MALE Shield Wire PINOUTS...
8.31 SARTORIUS TO GWY-00 (EC-P-104-00) GWY-00 SIDE SATORIUS (COM1) SIDE 2 mtr. WIRE OUTS DB9 MALE SIGNAL FROM Shield Wire (RS232) SATORIUS Pin # SIGNALS Pin # SIGNALS YELLOW GREEN BLACK DB9 MALE Shield Wire PINOUTS...
AB MICROLOGIX SERIES PLCs TO GWY-S7 (EC-G7-027A-00) GWY-S7 SIDE AB MICROLOGIX SIDE 2 mtr. MINIDIN 8 PIN MALE DB9 MALE (RS232) Shield Wire (RS232) SIGNALS Pin # Pin # SIGNALS 8 PIN MINIDIN CONNECTOR DB9 MALE Shield Wire PINOUTS PINOUTS...
A B SLC DF1 PORT TO GWY-S7 (EC-G7-027B-00) AB SLC SIDE GWY-S7 SIDE 2 mtr. DB9 MALE DB9 FEMALE Shield Wire (RS232) (RS232) Pin # SIGNALS SIGNALS Pin # DB9 MALE DB9 FEMALE Shield Wire to DB9 body PINOUTS PINOUTS...
SIEMENS STEP 7 MICRO (S7-200) PLC TO GWY-S7 (EC-G7-077-00) GWY-S7 SIDE SIEMENS S7-200 SIDE 2 mtr. DB9 MALE DB9 MALE (RS485) Shield Wire (RS485) SIGNALS Pin # Pin # SIGNALS DB9 MALE Shield Wire to DB9 body PINOUTS Note: These details are also applicable to Siemens S7-300...
GE 90 SERIES PLC TO GWY-S7 (EC-G7-002-00) GE 90 SERIES SIDE GWY-S7 SIDE 2 mtr. DB9 MALE Shield Wire (RS485) DB15 MALE (RS485) Pin # SIGNALS # Pin # SIGNALS EARTH DB9 MALE PINOUTS Shield Wire DB15 MALE PINOUTS...
SIEMENS S7-300 PLC TO GWY-S7 (EC-G7-077-00) SIEMENS S7-300 SIDE GWY-S7 SIDE 2 mtr. DB9 MALE DB9 MALE Shield Wire (RS485) (RS485) SIGNALS Pin # Pin # SIGNALS DB9 MALE Shield Wire to DB9 body PINOUTS Note: These details are also applicable to Siemens S7-200...
9.10 AB SLC DH485 PORT TO GWY-S7 (EC-G7-007-00) GWY-S7 SIDE AB SLC SIDE 2 mtr. 8 PIN MODULAR CONNECTOR DB9 MALE (RS485) Shield Wire (RS485) Pin # SIGNALS Pin # SIGNALS SHIELD 8 PIN MODULAR CONNECTOR PINOUTS Shield Wire DB9 MALE PINOUTS FRONT VIEW R.H.S.
9.12 AROMAT FP1 TO GWY-S7 (EC-G7-015B-00) GWY-S7 SIDE ARPMAT FP1 SIDE 2 mtr. DB9 MALE DIN CONNECTOR (RS485) Shield Wire MALE (RS485) Pin # SIGNALS Pin # SIGNALS DIN CONNECTOR PINOUTS Shield Wire DB9 MALE PINOUTS...
9.13 AROMAT FP2 TO GWY-S7 (EC-G7-015D-00) AROMAT FP2 SIDE GWY-S7 SIDE 2 mtr. DB9 MALE DB9 MALE Shield Wire (RS232) (RS232) SIGNALS Pin # Pin # SIGNALS Shield Wire to DB9 body DB9 MALE PINOUTS...
10.1 SIEMENS S7-300 SERIES PLC TO GWY-S8 (EC-G8-077-00) SIEMENS S7-300 SIDE GWY-S8 SIDE 2 mtr. DB9 MALE DB9 MALE (RS485) Shield Wire (RS485) SIGNALS Pin # Pin # SIGNALS DB9 MALE Shield Wire to DB9 body PINOUTS...
11.2 IBM CABLE FOR GWY-S7 PC SIDE GWY-S7 SIDE 2 mtr. DB9 MALE DB9 FEMALE Shield Wire (RS232) (RS232) SIGNALS Pin # SIGNALS Pin # DB9 FEMALE DB9 MALE PINOUTS Shield Wire PINOUTS...
Page 89
Pins 3 and 4 on any one of GWY-00 port should be shorted at power-on. Wait for atleast 1 second. After the ‘OK’ LED starts blinking, remove the short. Now GWY-00 permanently waits for IBM download.
Page 90
This string is used to test other port by LOOP-BACK method. If the port is functional, Gateway send the same string back to the software. User must test all three signal levels on both the serial ports. Test Setup: Gateway unit (GWY-00) Gateway Setup Software IBM cable...
ADDENDUM FOR SPECIAL GATEWAY MODELS Special Gateway Models Communication Ports of Special Gateway Models Configuration of Special Gateway Models Dimensional Details and Mounting Instructions for Special Gateway Models Supported PLC’s List for Special Gateway Models...
Special Gateway Models Gateway has some special models which have different hardware as compared to GWY-00. Operation of all Gateways is the same. This section presents details of all the hardware differences and special require- ments for operating these hardwares. This section has the details of GWY-01, GWY-02, GWY-04, GWY-05, GWY-06, GWY-08 and GWY-S7.
Page 93
GWY-04 Power Supply : 5 VDC +/- 5 % regulated on PLC1 port, 120 mA max Communication : Two ports as follows: PLC1: RS485-For configuration and PLC communication PLC 1 (RS485) PLC2: RS485-For PLC communication PLC 1 Indications : PLC1 LED - for PLC1 port status OK LED - for Gateway status PLC 2 PLC2 LED - for PLC2 port status...
Page 94
GWY-06 Power Supply : 24 VDC +/- 10 % regulated on PLC1 port, 50 mA max Communication : Two ports as follows: PLC1: RS232-For configuration and PLC PLC 1 (RS232) communication PLC2: RS485-For PLC communication PLC 1 Indications : PLC1 LED - for PLC1 port status OK LED - for Gateway status PLC 2 PLC2 LED - for PLC2 port status...
Page 95
Storage: - 40 to 90 °C Humidity : 10% to 90% (Non condensing) PENDING LR 109782-2 Renu Electronics Pvt. Ltd. Immunity to ESD : Level 3 as per IEC1000-4-2 Survey No. 2/6, Baner Road, Pune-411045 INDIA Immunity to Transients : Level 3 as per IEC1000-4-4...
Communication Ports of Special Gateway Models Gateway has two communication ports for communication with PLC’s and other devices. User must ensure proper communication cable for error free communication. This section explains various types of ports in Special Gateway models. RS232 port Mentioned below are the types of RS232 port available in Special Gateway models.
Page 97
PLC 1 PORT OF GWY-S7 PLC1 port of GWY-S7 has a DB9 female type connector and is compatible with RS232C, RS422, RS485 and CMOS signal levels. Pin outs of this port are as given below: RX- (RS422/RS485) RX+ (RS422/ TX- (RS422/RS485) RXD (RS232C/CMOS) TXD (CMOS) TXD (RS232C)
Page 98
User can convert RS485 4 wire + Signal Ground system to a 2 Wire + Signal Ground system by shorting following signals in the communication cable: Note: If user has attached shield to Earth on Device end, leave the shield open on Gateway end. If user has connected shield to Signal Ground on Device end, connect shield to Signal Ground on Gateway end.
Configuration of Special Gateway Models: Special Gateways communicate with IBM on COM1 / PLC1 port for configuration of Gateway. GWY-01, GWY-02, GWY-05 and GWY-06 have RS232 PLC1 port and need a “Y” Cable, similar to the cable shown in the figure below, for configuration. One end of the cable connects to Gateway which has both power and communication signals, the second end connects to the device (PLC) for power and the third end connects to IBM PC for communication.
Page 100
GWY-S7 has PLC1 port compatible with RS232/RS422/RS485 and CMOS port. IBM communication can be done on PLC1 / COM1 port only. Downloading procedure is same as that of GWY-00. Use Gateway Setup V2.xxx for creating and downloading configuration. I BM download cable is as shown below:...
Dimensional Details and Mounting Instructions for Special Gateway Models: This section has dimensional details and mounting instructions for GWY-01, GWY-02, GWY-04, GWY-05, GWY-06 and GWY-08. Dimensional details & Mounting instructions for GWY-S7 are same as GWY-00. Attach Termination 1. TX+ 2.
Page 102
For mounting Gateway on a DIN rail refer to the following drawing and follow the instructions given below. PLC 1 (RS485) PLC 1 (RS485) PLC 1 PLC 1 PLC 2 PLC 2 GWY-08 GWY-08 LR 109782-2 LR 109782-2 PLC 2 (RS485) PLC 2 (RS485) Pull the DIN rail clip out.
Supported PLC’s List for Special Gateway Models Following Table shows the list of supported PLC’s for Gateway models GWY-01 to GWY-08 with their power capability and communication signal levels. This table can be used to find out different configurations for any given model.