9-4. TEST POINT DIAGRAM
PMFY-P06NBMU-E
PMFY-P06NBMU-E
1
CN27
Connector
(Damper)
CN25
Connecter
(Humidifier)
CN6V
Vane motor output
(MV)
CN52
Remote indication
CN51
Centrally control
CN41
HA terminal-A
CN60
Linear expansion
valve output (LEV)
CN20
Room temperature
thermistor (TH21)
CN21
Pipe temperature
thermistor/Liquid
(TH22)
CN29
Pipe temperature
thermistor/Gas
(TH23)
CN31
Drain sensor (DS)
LED2
Power supply (R.B)
PMFY-P08NBMU-E
PMFY-P08NBMU-E
SW2
SW3
Capacity setting
Function setting
CN3A
Connect to the terminal block (TB15)
(MA-Remote controller connecting wire)
Between 1 1 to 3 3 8.7-13V DC (Pin1 1 (+))
PMFY-P12NBMU-E
PMFY-P12NBMU-E
1
CN32
Connector
SW4
(Remote switch)
Model selection
CN2M
Connect to the terminal block (TB5)
(M-NET transmission connecting wire)
24-30V DC (non-polar)
26
PMFY-P15NBMU-E
PMFY-P15NBMU-E
1
CNP
Drain pump output
(DP)
Between 1 1 to 3 3
208-230V AC
CND
Connect to the
terminal block (TB2)
(Power supply for
indoor controller
board connecting
wire)
Between 1 1 to 3 3
208-230V AC
FUSE
6.3A 250V
FAN
Fan motor output
(MF)
LED1
Power supply (I.B)
(Indoor unit :
208-230V)
1