From the preceding page
Control modes
2-3. Thermo OFF mode
2. Fan
When the thermoregulating function changes to OFF, the indoor fan operates in
[Extra low].
2-4. Heat defrosting mode
The indoor fan stops.
3. Drain pump
No drain pump operation
However, when the control changes from COOL or DRY operation, the drain pump
operates for 3 minutes.
(1) Initial setting : OFF
4. Vane control
(Up/ down vane
change)
(2) Vane position :
(3) Restriction of vane position
1 The vane is horizontally fixed for the following modes.
(The control by the remote controller is temporarily invalidated and controlled by
the unit.)
• Thermo OFF
• Stand by (hot adjust) [Extra low] mode
• Heat defrost mode
Control details
HEAT···[last setting]
When changing the mode from exception of HEAT to HEAT
operation ···[Downward C]
Horizontal
Downward A
Downward B
Downward C Swing
18
Remarks