DIP Switches
Reverse Polarity Mode
Local Energy
Note: You may use different operation modes for the circuits. The DIP switch settings 1 to 3 for each switch (S1
and S2) must be set to the same position.
Mounting
1.
Bring the plug-in module into position with the horizontal terminal lettering facing the front side of the control
panel. Slide the plug-in module carefully into position along the guide rails (refer to Figure 2, Page 5, Item 1)
2.
Ensure that the connections seat into the slot properly (refer to Figure 2, Page 5, Item 2).
3.
Press down softly until the snap-fit hook locks into place (refer to Figure 2, Page 5, Item 3).
Fire
Gas Alarm
Power
Supervisory
Silenced
Trouble
DRILL
RESET
SILENCE
ACK
?
@
_
. : ,
A a
Figure 2 Installing the FPE-1000-CITY City Tie Plug-in Module
To remove a plug-in module, press the snap-fit hook carefully from left to right and pull the board toward the panel
front.
Wiring
No special wire is required for addressable loops. The wire can be untwisted, unshielded, solid or stranded as long
as it meets the National Electric Code 760-51 requirements for power-limited fire protective signaling cables.
Observe a maximum circuit resistance of 65 Ω.
Note: Use the appropiate DIP switch setting at the module to obtain the desired operation mode (refer to Figure 1,
Page 4).
Reverse Polarity Mode
The FPE-1000-CITY connects the FPA-1000 Analog Addressable Fire Panel to either a single set or a pair of dual
leased telephone company (telco) lines in NFPA 72 Remote Station applications. The FPE-1000-CITY relays system
alarm status information from the control panel to a monitoring station.
In normal conditions, the FPE-1000-CITY sends a steady current to a monitoring station. In an alarm condition, it
reverses the polarity of the output current. The FPE-1000-CITY signals a trouble condition by interrupting the output
voltage and current.
The default setting is fire alarm for circuit 1 and supervisory for circuit 2.
NOTICE!
Intended for connection to a polarity reversal circuit of a remote station receiving unit having
compatible ratings.
Terminal
Default setting
ALM - | +
Fire Alarm
SUP - | +
Supervisory
Legend
M
Monitoring Station
Bosch Security Systems, Inc.
S1 = SUP
1
2
ON
ON
OFF
OFF
1
3
1
3
1
ON
ON
OFF
OFF
2
ALM -
+
-
SUP
+
Figure 3 Reverse Polarity Mode
en
5
S2 = ALM
2
3
ON
ON
OFF
OFF
M
F.01U.078.100 | 04 | 2011.11

Advertisement

Table of Contents
loading

Table of Contents