Specifications - Bosch FPE-1000-CITY Installation Manual

City tie plug-in module
Table of Contents

Advertisement

Available languages

Available languages

  • ENGLISH, page 1
6
en
Local Energy Mode
The FPE-1000-CITY connects Local Energy signaling devices to the FPA-1000 fire panel for auxiliary service
operation.
Refer to the FPA-1000 Installation and Operation Guide for a listing of compatible Gamewell devices.
Terminal
ALM - | +
Connects to Municipal Master Box
SUP - | +
Not used

Specifications

Circuit resistance
Wire gauge
Operating temperature
Storage temperature
Relative humidity
Reverse Polarity Mode
Nominal Voltage
Output current
Supervisory/standby current
Local Energy Mode
Type of connection
Alarm, trip coil
Alarm current
Supervisory/standby current
Trip coil resistance
Nominal coil voltage
F.01U.078.100 | 04 | 2011.11
65 Ω
2
12 to 18 AWG (3.3 mm
to 0.8 mm
32 °F to 120 °F (0 °C to 49 °C)
-4 °F to 140 °F (-20 °C to 60 °C)
Up to 93%, non-condensing
24 V DC nominal (26.4 V DC maximum), power-limited, supervised
33 mA maximum
5 mA
In series
24 V DC
250 mA (momentary, <1 ms)
<50 mA DC
14.5 Ω
3.65 V DC, power-limited, supervised
ALM -
ALM+
SUP-
SUP+
Figure 4 Local Energy Mode