Carrier PA17NA Installation Instructions Manual page 9

Split-system, 2-stage air conditioner with r-410a refrigerant 2-5 tons
Table of Contents

Advertisement

S R- -410A refrigerant operates at 50- -70 percent higher pressures than R- -22. Be sure that servicing equipment and replacement
components are designed to operate with R- -410A refrigerant
S R- -410A refrigerant cylinders are rose colored.
S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
S R- -410A refrigerant systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose
when charging into suction line with compressor operating
S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low- -side retard.
S Use hoses with 700 psig service pressure rating.
S Leak detectors should be designed to detect HFC refrigerant.
S R- -410A refrigerant, as with other HFCs, is only compatible with POE oils.
S Vacuum pumps will not remove moisture from oil.
S Do not use liquid- -line filter driers with rated working pressures less than 600 psig.
S Do not leave R- -410A suction line filter driers in line longer than 72 hours.
S Do not install a suction- -line filter drier in liquid line.
S POE oils absorb moisture rapidly. Do not expose oil to atmosphere.
S POE oils may cause damage to certain plastics and roofing materials.
S Wrap all filter driers and service valves with wet cloth when brazing.
S A factory approved liquid- -line filter drier is required on every unit.
S Do NOT use an R- -22 TXV.
S If indoor unit is equipped with an R- -22 TXV or piston metering device, it must be changed to a hard shutoff R- -410A TXV.
S Never open system to atmosphere while it is under a vacuum.
S When system must be opened for service, recover refrigerant, evacuate then break vacuum with dry nitrogen and replace filter driers.
Evacuate to 500 microns prior to recharging.
S Do not vent R- -410A refrigerant into the atmosphere.
S Do not use capillary tube coils.
S Observe all warnings, cautions, and bold text.
S All indoor coils must be installed with a hard shutoff R- -410A TXV metering device.
Always Ask For
R- -410A REFRIGERANT QUICK REFERENCE GUIDE
9