Carrier PA17NA Installation Instructions Manual

Split-system, 2-stage air conditioner with r-410a refrigerant 2-5 tons

Advertisement

Quick Links

NOTE: Read the entire instruction manual before starting the
installation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other
conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your
distributor or branch for information or assistance. The qualified
installer or agency must use factory- -authorized kits or accessories
when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,
and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions included in
literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code ( NEC ) NFPA 70.
In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.
Recognize safety information. This is the safety- -alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand
these signal words; DANGER, WARNING, and CAUTION. These
words are used with the safety- -alert symbol. DANGER identifies
the most serious hazards which will result in severe personal injury
or death. WARNING signifies hazards which could result in
personal injury or death. CAUTION is used to identify unsafe
practices which would result in minor personal injury or product
and property damage. NOTE is used to highlight suggestions
which will result in enhanced installation, reliability, or operation.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Before installing, modifying, or servicing system, main
electrical disconnect switch must be in the OFF position.
There may be more than 1 disconnect switch. Lock out and
tag switch with a suitable warning label.

INSTALLATION RECOMMENDATIONS

NOTE: In some cases noise in the living area has been traced to
gas pulsations from improper installation of equipment.
1. Locate unit away from windows, patios, decks, etc. where
unit operation sound may disturb customer.
2. Ensure that vapor and liquid tube diameters are appropriate
for unit capacity.
3. Run refrigerant tubes as directly as possible by avoiding un-
necessary turns and bends.

Installation Instructions

! !
.
SPLIT- -SYSTEM, 2- -STAGE AIR CONDITIONER
WITH R- -410A REFRIGERANT
4. Leave some slack between structure and unit to absorb vi-
bration.
5. When passing refrigerant tubes through the wall, seal open-
ing with RTV or other pliable silicon- -based caulk. (See Fig.
1.)
6. Avoid direct tubing contact with water pipes, duct work,
floor joists, wall studs, floors, and walls.
7. Do not suspend refrigerant tubing from joists and studs with
a rigid wire or strap which comes in direct contact with
tubing.(See Fig. 1.)
8. Ensure that tubing insulation is pliable and completely sur-
rounds vapor tube.
9. When necessary, use hanger straps which are 1 in. (25.4
mm) wide and conform to shape of tubing insulation. (See
Fig. 1.)
10. Isolate hanger straps from insulation by using metal sleeves
bent to conform to shape of insulation.
OUTDOOR WALL
CAULK
INSULATION
THROUGH THE WALL
HANGER STRAP
(AROUND SUCTION
TUBE ONLY)
1" (25.4 mm)
MIN
Fig. 1 - - Connecting Tubing Installation
The outdoor unit contains system refrigerant charge for operation
with AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
field- -supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information
located on control box cover and/or in the Check Charge section of
this instruction.
IMPORTANT: Maximum liquid- -line size is 3/8- -in. OD for all
residential applications including long line.
IMPORTANT: Always install the factory- -supplied liquid- -line
filter drier. If replacing the filter drier, refer to Product Data Digest
for appropriate part number. Obtain replacement filter driers from
your distributor or branch.
PA17NA
2 - - 5 TONS
INDOOR WALL
LIQUID TUBE
SUCTION TUBE
JOIST
INSULATION
SUCTION TUBE
LIQUID TUBE
SUSPENSION
A07588

Advertisement

Table of Contents
loading

Summary of Contents for Carrier PA17NA

  • Page 1: Installation Instructions

    PA17NA SPLIT- -SYSTEM, 2- -STAGE AIR CONDITIONER WITH R- -410A REFRIGERANT 2 - - 5 TONS Installation Instructions NOTE: Read the entire instruction manual before starting the installation. SAFETY CONSIDERATIONS 4. Leave some slack between structure and unit to absorb vi- bration.
  • Page 2: Installation

    INSTALLATION Make Piping Connections Check Equipment and Job Site WARNING UNPACK UNIT Move to final location. Remove carton taking care not to damage PERSONAL INJURY AND ENVIRONMENTAL unit. HAZARD Inspect Equipment Failure to follow this warning could result in personal injury or death.
  • Page 3 Outdoor Unit Connected to Factory Approved Indoor Unit Outdoor unit contains correct system refrigerant charge for operation with factory approved AHRI rated indoor unit when connected by 15 ft. (4.57 m) of field- -supplied or factory- -accessory tubing, and factory supplied filter drier. Check refrigerant charge for maximum efficiency.
  • Page 4 Table 2 – Accessory Usage REQUIRED FOR REQUIRED FOR LONG LINE SEA COAST ACCESSORY APPLICATIONS* APPLICATIONS (Within 2 miles/3.22 km) Compressor Start Assist Capacitor and Relay Crankcase Heater (standard on some units) Hard Shut--- Off TXV (Standard with factory ---approved indoor unit) Support Feet Recommended * For tubing line sets between 80 and 200 ft.
  • Page 5: System Functions And Sequence Of Operation

    OF OPERATION Instructions. The FV4C utilizes an Easy Select control board that The PA17NA models utilize a 2-stage cooling indoor thermostat. allows the installing technician to select proper airflows. This fan With a call for first stage cooling, the outdoor fan and low-stage coil has an adjustable blower- -off delay factory set at 90 sec.
  • Page 6: Troubleshooting

    Check Charge TROUBLESHOOTING The PA17NA units may be charged in high- - or low- -stage If the compressor fails to operate with a cooling call, the table compressor operation. Factory charge amount and desired below (Resistance table) can be used to verify if there is any subcooling are shown on unit rating plate.
  • Page 7: Major Components

    MAJOR COMPONENTS CARE AND MAINTENANCE 2- - Stage Compressor For continuing high performance and to minimize possible equipment failure, periodic maintenance must be performed on this The 2- -stage compressor contains motor windings that provide equipment. 2- -pole (3500 RPM) operation. Frequency of maintenance may vary depending upon geographic Compressor Internal Relief areas, such as coastal applications.
  • Page 8 TWO-STAGE Two-Stage Variable Speed THERMIDISTAT AIR CONDITIONER Air Conditioner Fan Coil Thermidistat RVS/Heat Stage 2 O/W2/B Heat Stage 1 W/W1 REMOVE J2 JUMPER FOR Compressor Low HEAT STAGING Compressor High Y/Y2 Y/Y2 24VAC Hot Heating REMOVE J1 FOR 24VAC Hot Cooling DEHUMIDIFY MODES Dry Contact 1...
  • Page 9 R- -410A REFRIGERANT QUICK REFERENCE GUIDE S R- -410A refrigerant operates at 50- -70 percent higher pressures than R- -22. Be sure that servicing equipment and replacement components are designed to operate with R- -410A refrigerant S R- -410A refrigerant cylinders are rose colored. S Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.
  • Page 10 Catalog No: IM---PA17NA ---02 Copyright 2012 Payne Heating & Cooling S 7310 W. Morris St. S Indianapolis, IN 46231 Edition Date: 09/12 Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations. Replaces: IM--- PA17NA--- 01...