Clamp 2)
(Accessory)
Wiring through hole (left)
Transmission wiring from the outside unit
(To the TO OUT/D UNIT F1, F2 terminals)
NOTES
• Use ring-type crimp style terminal for connections to the
power terminal block. (Refer to Fig. 6)
Also, insulate the crimped area by attaching an insula-
tion sleeve, etc.
If these are not available, see the following section.
(a) Wiring of different thicknesses cannot be connected
to the power terminal block.
(A loose connection could cause abnormal heating.)
(b) When connecting wire of the same diameter, make
the connection as shown in the figure 7.
• Use an appropriate screwdriver for tightening the termi-
nal screw.
Using a screwdriver that is too small could damage the
screw head and prevent proper tightening.
• Over tightening the terminal screw could damage the
screw.
Refer to the Table 4 for the terminal screw tightening
torque.
• When fastening the wire, use the included clamp 2) so
as not to apply tensile force to the wire connection and then securely fasten the wire. Also, after wiring is
completed, organize the wiring so that the EL. COMPO. BOX lid does not pop up and then properly replace
the EL. COMPO. BOX lid.
Make sure no wires are pinched when replacing the EL. COMPO. BOX lid.
Always use the wire through hole to protect the wires.
• Do not pass the transmission wiring and power supply wiring through the same locations and outside of the
unit keep them separated by at least 2 in..
Not doing so could cause the transmission wiring to pick up electric noise (external noise) and result in a
malfunction or breakdown.
• After the wiring working is complete, use sealer (field supply) to seal closed the wire through hole.
(Entry by small animals, etc., could cause a malfunction.)
English
Transmission wiring from the indoor unit
(To the TO IN/D UNIT F1, F2 terminals)
Ground terminal
A1P
TO IN/D UNIT TO OUT/D UNIT
F1 F2 F1 F2
Terminal block
Power supply wiring
(To the terminal block
L1, L2 terminals)
Ground wire
Clamp 2)
(Accessory)
Wiring through
hole (right)
Insulation sleeve
Ring-type crimp
style terminal
Fig. 6
Connect wires of the
Do not connect
same gauge to both
wires of the same
sides.
gauge to one side.
Fig. 7
Table 4
Terminal screw size
M3.5 (COOL/HEAT SELECTOR/transmission
wiring terminal block (A1P))
M4 (Power supply terminal block)
M4 (Ground terminal)
Wire
Wire fitting
Clamp 2)
(Accessory)
Electric wire
Do not connect
wires of different
gauges.
Tightening torque (ft · lbf)
0.58-0.72
0.87-1.06
1.12-1.37
14