Installing The Fireplace; Step 1. Locating The Fireplace; Step 2. Framing The Fireplace - Heat & Glo LCOR-HVB-IPI Owner's Manual

Hide thumbs Also See for LCOR-HVB-IPI:
Table of Contents

Advertisement

3

Installing the Fireplace

Step 1. Locating the Fireplace

The diagram below shows space and clearance require-
ments for locating a fireplace within a room.
GLASS
PIER-HVB-IPI
TOP VIEW
36"
GLASS
GLASS
ST-HVB-IPI
TOP VIEW
GLASS
36"
Figure 4.
Fireplace Dimensions and Locations
Clearance Requirements
The top, back, and sides of the fireplace are defined by
stand-offs. The minimum clearance to a perpendicular wall
extending past the face of the fireplace is one inch (25 mm).
The metal ends of the fireplace may NOT be recessed into
combustible construction.
GLASS
RCOR-HVB-IPI
GLASS
TOP VIEW
GLASS
36"
36"
36"
36"
GLASS
36"
LCOR-HVB-IPI
TOP VIEW
GLASS
Minimum Clearances
from the Fireplace to Combustible Materials
Glass Sides or Ends .......... 36 .................... 914
Floor ................................... 0 ....................... 0
Rear Vent ........................... 1/2 ..................... 13
Metal Sides or Ends .......... 1/2 ..................... 13
Top ................................... 2 1/2 ................... 64
Ceiling* .............................. 31 .................... 787
* The clearance to the ceiling is measured from the top of
the unit, excluding the standoffs (see Figures 37 & 38).
The distance from the unit to combustible construction is to
be measured from the unit outer wrap surface to the com-
bustible construction, NOT from the screw heads that se-
cure the unit together.
Minimum Clearances
from the Vent Pipe to Combustible Materials
Vertical Sections. ............. 1 ................ 25
Horizontal Sections
Top ..................................... 3 ................ 75
Bottom ............................... 1 ................ 25
Sides ................................. 1 ................ 25
At Wall Firestops
Top .................................. 2 1/2 ............ 63.7
Bottom .............................. 1/2 ............... 13
Sides ................................. 1 ................ 25
For minimum clearances, see the direct vent termination
clearance diagrams on pages 30 and 31 in this manual.

Step 2. Framing the Fireplace

Fireplace framing can be built before or after the fireplace is
set in place. Framing should be positioned to accommo-
date wall coverings and fireplace facing material. The dia-
gram below shows framing reference dimensions.
CAUTION: MEASURE FIREPLACE DIMENSIONS AND
VERIFY FRAMING METHODS AND WALL COVERING
DETAILS BEFORE FRAMING.
WARNING: FRAMING DIMENSIONS ASSUME
!
USE OF 1/2 INCH THICK WALL COVERING
MATERIALS ON EXTERIOR OF FRAMING ONLY AND
NO SHEETROCK ON INTERIOR OF FRAMING.
18
Inches
mm
Inches
mm

Advertisement

Table of Contents
loading

This manual is also suitable for:

St-hvb-ipiRcor-hvb-ipiPier-hvb-ipi

Table of Contents