Honeywell Heat/1Cool - T841A1563 Premier 2 Stage Thermostat User Manual page 74

Heat pump thermostat
Table of Contents

Advertisement

INTERTHERM/MILLER/NORDYNE
Existing
Function
Terminals
Common
X
Power
R
Compressor
Y
1st Stage
Heat
Auxiliary
W2
Heat
Fan
G
Outdoor
T
Thermistor
Em. Heat
K
C/O Valve
W1
Cool
System Monitor/
Z
System Defrost
For best performance, use a NEMA rated transformer.
Terminal B (C, X) must be connected to transformer common.
Configure O/B (select models) in Installer Setup.
Leave factory-installed jumper W1-Y1 (Y) in place.
Tape off. Electronic thermostat replaces outdoor reset with improved zero
droop performance.
70-6627 • 72
Electromechanical
B
B
B
R
R
R
Y
Y
Y1
W
W
W
G
G
G
T
T
T
X2
X2
X2
O
O
O
F
F
F
Electronic Replacement or Upgrade
®
Chronotherm
III
C
C
R
R
or
Y1
Y
Y
W1
W1
W2
W2
G
G
E
E
O
O
O
L
L
To eliminate auto fan in EM. Heat mode, see page 9.
Use Aux terminal for Auxiliary heat and configure W2 cycle rate to NC.
LED is energized when terminal is powered.
L terminal is powered continuously when thermostat is in Em. Ht. position.
Chronotherm
IV
C
C
C
R
R
R
Y1
Y
Y1
W1
W1
W1
W2
W2
W2
G
G
G
E
E
E
or
or
O/B
O
O
O/B
L
L
L
C
R
Y1/W1
Aux.
G
E
O/B
L
M13160