TYPICAL 3700, 3900, 4400, 6500, 7100, 9200 (3600 SERIES THERMOSTAT) ALTERNATIVE REPLACEMENTS
Existing
Function
Terminals
or
Common
C/X
X
Power
R
Compressor
Y
1st Stage
W1
Heat
Aux. Heat
W2
Fan
G
Defrost
B
C/O Valve
O
Cool
System Monitor/
L
System Defrost
EM. Heat
E
Multiple Aux.
–
Heat Loads
LED Indication
–
EM. Heat
P
2nd Stage
–
Compressor
Configure O/B (select models) in Installer Setup.
LED is energized when terminal is powered.
Terminal is for multiple auxiliary heat loads such as contactors, sequencers,
or relays.
Terminal X (C) must be connected to transformer common.
Do not remove factory-installed jumper.
Optional CHECK LED on T8611G1004. See Fig. 26.
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
Electromechanical
X
X
X
R
R
R
Y
Y
Y1
–
W1
W1
W2
W2
W2
G
G
G
B
B
B
O
O
O
L
X1
E
E
E
W3
W3
W3
–
X2
X2
–
–
–
–
–
–
T8611R1059 (3600A-381)
Electronic Replacement or Upgrade
Chronotherm
®
III
C
C
R
R
or
Y1
Y
Y
W1
W1
W2
W2
G
G
B
B
O
O
O
L
L
E
E
X1 X2
–
P
–
–
–
Field-installed X2 to X jumper (provided).
If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
terminal.
L terminal is powered continuously when thermostat is in Em. Ht. position.
Defrost is available on T8611R1000 only.
Models 3700, 3900 and 6500 require connection of O and B terminals.
When W2 is not used, configure W2 cycle rate to NC.
EVCON/COLEMAN
Chronotherm
IV
C
C
C
R
R
R
Y1
Y
Y1
W1
W1
W1
W2
W2
W2
G
G
G
B
B
B
or
or
O/B
O
O
O/B
L
L
L
E
E
E
–
–
X1 X2
–
–
–
–
–
–
70-6627 • 53
C
R
Y1/W1
–
Aux.
G
B
O/B
L
E
–
–
W2
M13174