Gas Conversion; Gas Supply - Kenmore 153.336930 Use & Care Manual

30/40 gallon tall
Hide thumbs Also See for 153.336930:
Table of Contents

Advertisement

• For your safety, the following procedures should be
performed
by a qualified technician
as it involves
disconnection
of gas piping and leak testing.
• Do not connect a natural gas water heater to an L.P.
gas supply.
• Do not connect an L.P. gas water heater to a natural
gas supply.
A. Remove
the Manifold/Burner
Assembly
1.
Turn off the gas supply to the water heater at the manual
gas shut-off valve. This valve is typically located beside the
water heater.
Note the position of the shut-off valve in the
open/on position, then proceed to turn it off.
2.
On the lower front of the water heater, locate the gas control
valve/thermostat.
3.
Turn the gas control/temperature
knob to the "OFF" position.
With the unit shut-off, allow sufficient time for the water
heater to cool before performing any maintenance.
4.
Remove the outer door.
5.
Remove the two screws securing
the installed
manifold
door assembly to the combustion chamber (Figure 11).
6.
Disconnect the following from the gas control valve/thermostat:
pilot tube, igniter wire, and manifold tube. See Figure 11.
7.
Using needle nose pliers, disconnect
the white and red
thermopile
wires from the gas control
valve/thermostat
(Figure 11).
8. Grasp the manifold tube and push down slightly to free the
manifold tube and pilot tube.
9.
Carefully remove the manifold/burner assembly from the burner
compartment. NOTE: Be sure not to damage internal parts.
B. Convert
the Gas Control
Valve/Thermostat
1.
Remove the cap (shown in Figure 12).
2.
Remove the conversion fitting by turning it counter-clockwise
with a fiathead screwdriver.
3.
Thread the opposite end of the conversion fitting into the opening
by turning it clockwise, then tighten it with a flathead screwdriver.
a.
LP GAS: If you are converting the unit to use LP gas
(propane), verify that "LP" is marked on the exposed end
of the fitting. "LP" must face outward (toward you.) See
GAS
CONTROL/
TEMPERATURE
KNOB
PIEZO
IGNITER
BUTTON
PILOTTUBE
WIRE
CONNECTIONS
- MANIFOLD
TUBE
OUTER
DOOR
NOT SHOWN
MANIFOLD SCREW (2) --
SWITCH
DOOR
MANIFOLD
COMPONENT
BLOCK
FIGURE 11,
4.
C.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
16
Figure 12. If "NAT" faces outward, repeat step 2.
b.
NATURAL GAS: If you are converting the unit to use
natural gas, verify that "NAT" is marked on the exposed
end of the fitting. "NAT" must face outward (toward you.)
See Figure 12. If "LP" faces outward, repeat step 2.
Replace the cap.
Install the Conversion
Manifold/Burner
Assembly
Check the door gasket for damage or imbedded debris prior
to installation.
Inspect the view port for damage and replace as required.
Insert the conversion
manifold/burner
assembly
into the
burner compartment, making sure that the tip of the manifold
tube engages in the slot of the bracket inside the combustion
chamber.
NOTE: For 30 gallon models, the LP manifold/
burner assembly is identified by a yellow square (label) on
the packaging.
For 40 gallon models, the LP manifold/burner
assembly is identified by a green square on the packaging.
Inspect the door gasket and make sure there is no fiberglass
insulation between the gasket and the combustion chamber.
Replace the two screws that secure the manifold/burner
assembly door to the combustion
chamber,
then tighten
them securely. There should
be no space between
the
gasket
part of the manifold
door and the combustion
chamber.
IMPORTANT:
Do not operate the water heater
if the door gasket does not create a seal between
the
manifold door and the combustion chamber.
Reconnect
the manifold tube and pilot tube to the gas
control valve/thermostat
(Figure 11). Do not cross-thread
or apply any thread sealant to the fittings.
IMPORTANT: If
you were supplied with a new ferrule nut in a parts kit, follow
these steps to connect the pilot tube:
A.) Install the ferrule nut into the gas valve at the pilot tube
location, hand tight only. B.) Insert the pilot tube into the
ferrule nut until the tube bottoms out, then tighten the nut with
a 7/16" wrench until the crimp connection seals to the pilot tube.
C.) Continue to tighten until the nut is tight in the gas valve.
Connect the white and red thermopile
wires to the gas
control valve/thermostat.
See Figure 11.
Reconnect the igniter wire.
Turn the gas supply on and follow the Lighting Instructions.
With the main burner tit, check for leaks at the manifold and
pilot connections by brushing on an approved non-corrosive
leak detection solution.
If such a solution is not available,
use a mixture of hand dish washing soap and water (one
part soap to 15 parts water).
Bubbles forming indicate a
leak. Correct any leak found.
Verify proper operation; replace outer door.
GAS CONTROLVALVE/THERMOSTAT
f/CONVERSION
FITTING
_____
_
CA_ NATURAL GAS:
\\_-AJ_/J
"NAT"
FACES OUTWARD
(TOWARD
YOU).*
LP GAS:
"LP" FACES OUTWARD
(TOWARD
YOU).*
* ORIENTATION
MAY
VARY
FITTING
TO BE
TIGHT
FIGURE 12,

Advertisement

Table of Contents
loading

This manual is also suitable for:

153.336940153.336931

Table of Contents