Water Piping Pressure Test; Closed System/Thermal Expansion; Temperature And Pressure Relief Valve - Kenmore 153.336340 Owner's Manual

Mobile home gas water heater
Table of Contents

Advertisement

Water Piping Pressure
Test
Temperature
and Pressure
Relief Valve
If the water piping system is to be air pressure tested, the
water heater must be disconnected
from the water piping
system.
Failure to disconnect the water heater during air
pressure testing of the water piping system could result in
DEATH, SERIOUS BODILY INJURY, OR PROPERTY
DAMAGE.
This section is only for the manufacturer
installing the water
heater when the installation is to comply with H.UD. Standards.
When testing the water ways, H.U.D. standards state: "Water
distribution
system. All water
piping in the water distribution
system shall be subjected to a pressure test. The test shall be
made by subjecting the system to air or water at 100 psi for 15
minutes without toss of pressure. When air pressure is used,
the water heater shall not be connected during the test."
AIR PRESSURE
TESTING
HOT
WATER
_
OUTLET
WHEN
AIR TESTING,
REMOVE
THE
WATER
LINES
FROM
THE WATER
HEATER,
COLD
WATER
I "--I1_
_
INLET
FIGURE 20.
Closed
System/Thermal
Expansion
Property
Damage
Hazard
. A_lwater heaters eventually leak
• Do not install without adequate drainage,
As water
is heated,
it expands
(thermal
expansion).
In a closed
system, the volume
of water will grow. As the volume of water grows,
there will be a corresponding
increase
in water
pressure
due to
thermal
expansion.
Thermal
expansion
can cause premature
tank
failure (leakage).
This type of failure is not covered
under the limited
warranty. Thermal expansion can also cause intermittent
temperature-
pressure
relief valve operation:
water discharged
from the valve due
to excessive
pressure
build up. The temperature-pressure
relief valve
is not intended
for the constant
relief of thermal
expansion.
This
condition
is not covered
under the limited warranty.
A properly sized thermal expansion
tank should be installed
on all closed systems to control the harmful effects of thermal
expansion. Thermal expansion tanks are available from Sears
stores and through the Sears Service Centers.
Contact the
local
plumbing
inspector,
water
supplier
and/or
the Sears
Service Center for assistance
in controlling
these situations.
(For additional information, see the Troubleshooting
Guide later
in this manual.)
)losion
Hazard
Temperature-pressurereliefvalve
must complywith ANSI Z21.22-
CSA4.4 and ASME code.
• Properly sized temperature-
pressure
relief valve must be
installed in opening provided.
• Can result in overheating
and
excessive
tank pressure.
• Can cause serious injury or
death.
22
1"
MINIMUM
METAL
DRAIN
PAN
-_='-_
TEMPERATURE
AND
PRESSURE
(T&P)
RELIEF
VALVE
(OPTIONAL
TOP T&P
RELIEF
VALVE
NOT
SHOWN)
_--_-
DISCHARGE
PIPE
(DO
NOT
CAP OR PLUG)
PAN DRAIN
LINE
_
3/4"
ID
MINIMUM
DRAIN
LINE
TERMINATES
_P
EXTERNAL
TO BUILDING
FIGURE 21.
For protection against excessive pressures and temperatures,
a temperature and pressure relief valve must be installed in the
opening marked "T & P RELIEF VALVE." (See Figure 21). This
valve must be design certified by a nationally recognized testing
laboratory that maintains periodic inspection of the production
of listed equipment
or materials as meeting the requirements
for Relief Valves for Hot Water Supply Systems, ANSI Z21.22.
The function of the temperature
and pressure relief valve is to
discharge water in large quantities
in the event of excessive
temperature
or pressure developing
in the water heater. The
valve's relief pressure must not exceed the working pressure of
the water heater as stated on the rating plate.
IMPORTANT: Only a new temperature
and pressure relief valve
should be used with your water heater. Do not use an old or
existing valve as it may be damaged or not adequate for the
working
pressure of the new water heater. Do not place any
valve between the relief valve and the tank.
The Temperature
& Pressure
Relief Valve:
Must not be in contact with any electrical part.
Must be connected to an adequate discharge line.
Must not be rated higher than the working pressure shown
on the rating plate of the water heater.
The Discharge
Line:
Must not be smaller than the pipe size of the relief valve or
have any reducing coupling installed in the discharge line.
Must not be capped, blocked, plugged or contain any valve
between the relief valve and the end of the discharge line.
Must pass through
the structural
floor
and terminate
external to the building. In cold climates, it is recommended
that the discharge pipe be terminated at an adequate drain
inside the building.
Must be capable of withstanding 250°F (121°C)without distortion.
Must be installed to allow complete drainage of both the
valve and discharge line.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

153.336444

Table of Contents